background image

4/8 

Siemens 

QAX34.1 – Room unit with PPS2 interface 

CA2N1645en_02 

Building Technologies 

 

30 Jun 2009 

 

01884

 

 
 
 
 
 
 
Address plugs inside the housing 
They allow setting the address in cases where several 
room units are connected to one controller. 
The room units are delivered with address 1. 

 

Disposal 

 

The device is classified as waste electronic equipment in terms of the European Direc-
tive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste.  
The relevant national legal rules are to be adhered to.  
Regarding disposal, use the systems setup for collecting electronic waste. 
Observe all local and applicable laws. 

 

Engineering notes 

The device receives its power from the connected controller via the PPS2 interface 
(extra low voltage).

 

Only one room unit may be connected to a RX… room controller.  

A maximum of 5 room units may be connected to a PXC… automation station (they are 
identified by different settings of their address plugs) 

A twisted-pair cable is required for the connection to the controller.  
DESIGO RX uses four-core cables, DESIGO PX uses two-core cables (see the respec-
tive installation guides). Screening is not required. 
 

Mounting 

  The room unit is suitable for wall-mounting and for mounting on a recessed conduit 

box.  

  Do not mount in recesses, shelves, behind curtains or doors, or above or near heat 

sources. 

  Avoid exposure to direct sunlight or draughts.  

  The electrical wiring conduit must be sealed where it joins the room unit, to prevent 

the occurrence of draughts in the conduit which could affect the sensor. 

  The specified ambient conditions must be complied with.  

  Mounting instructions are printed on the room unit packaging.  

  A mounting kit is included with the unit. 

 

Installation notes 

Local installation regulations must be observed. 

The room unit is not protected against connection to AC 230 V.  
 
 
 

Address plugs 

STOP

  Note! 

Содержание QAX34.1

Страница 1: ...it is used in rooms controlled by an individual room control system to mea sure the room temperature and for operation of the room controller The functions of the LCD display are determined by the controller If manual fan speed control is enabled the room unit is suitable for control of a fan coil system It can also be used in conjunction with a DESIGO PXC automation station 1 The room unit incorp...

Страница 2: ...etpoint adjuster rocker switch for mode selection and fan speed selection plug in connectors and a socket for the commissioning and service tool or service terminal Both the housing and base are made of plastic Base unit Housing 80083 80084 Socket for the commissioning and service tool or service terminal 80166A Room temperature display and sequence heating or cooling Rocker switch for room temper...

Страница 3: ...ress the switch once to switch from a display of the current room temperature to a display of the setpoint Each further operation of the or switch raises or lowers the setpoint by 0 5 K or 1 0 F the unit of measurement is determined by the controller The controller also determines the maximum adjustment range allowed In normal operation the following may be displayed depending on the controller co...

Страница 4: ...oom units may be connected to a PXC automation station they are identified by different settings of their address plugs A twisted pair cable is required for the connection to the controller DESIGO RX uses four core cables DESIGO PX uses two core cables see the respec tive installation guides Screening is not required Mounting The room unit is suitable for wall mounting and for mounting on a recess...

Страница 5: ...ce tool initiates a wink command the type of controller connected will be displayed on the room unit For example Controller type Display RXC21 1 RXC30 1 Operating notes During operation and commissioning the LCD display also indicates errors as follows Display Description Error type C No communication with controller for more than 64 s 02 Firmware version e g Version 2 0 D Room temperature sensor ...

Страница 6: ...IGO RXC CA110334 DESIGO RXB RXL CM110381 DESIGO RXA CA2Z3884 DESIGO PX CA110396 Cable type 2 core or 4 core twisted pairs unscreened Connecting cable for service tool Off the shelf max 3 m Housing protection standard Protection standard to EN 60529 IP 30 Protection class Insulation protection class III Ambient conditions IEC 721 Operation Transport Ambient air conditions Class 3K5 Class 2K3 Temper...

Страница 7: ...voltage CP 1 Device supply Data PPS2 pos CP 2 Device supply Data PPS2 neg Bus connection looped to tool socket C 3 With LONWORKS bus DESIGO RXC CLA C 4 With LONWORKS bus DESIGO RXC CLB 5 8 Not used Standard type RJ45 tool socket 1 3206Z01 2 3 45 67 8 With LONWORKS bus DESIGO RXC CLA With LONWORKS bus DESIGO RXC CLB Not used Not used Not used Not used CP Data PPS2 CP Data PPS2 Connection diagram Ex...

Страница 8: ...ns QAX34 1 Room unit with PPS2 interface CA2N1645en_02 Building Technologies 30 Jun 2009 Dimensions 9 5 32 34 4 2 60 80088 90 100 56 60 56 All dimensions in mm 2000 2009 Siemens Switzerland Ltd Subject to change ...

Отзывы: