Path: Home > 0.5 OZS164… > Settings > Inputs > Fault input 1…2
Fault input 1...2
Digital inputs D1, D2 help connect potential-free status contacts. They work as fault
inputs.
Note
The following settings show how to configure fault inputs.
Select "Settings > Faults > Local > Fault input 1…2" to define behavior during
faults.
Data point
Explanation, example
F
ault input 1…2*
Default val.: (Blank)
Setting val:
Max. 20 characters
Customizable text for fault input. The
designation is displayed in the menu and
transmitted as part of the message.
Identical to data point in "Settings > Faults >
ocal > Fault input 1…2".
L
—
N
ormal position
Default val.: Open
Setting val:
Open,
Closed
Normal position specifies the contact position
deemed "No fault".
—
T
ext for: Logic 0*
Default val.: 0
Setting val:
Max. 20 characters
Logic 0: No fault.
Customizable text for fault input status, e.g.
ater press normal.
W
—
T
ext for: Logic 1*
Default val.: 1
Setting val:
Max. 20 characters
Logic 1: Fault.
Customizable text for fault input status, e.g.
ater press too low.
W
—
* Notes:
•
Note Section 2.4, Section "Update device web pages".
•
Delete the entry to reset to default text.
33 / 108
Siemens Web
server
CE1C5711en
Building Technologies
Commissioning
25.08.2010