Path: Home > 0.5 OZS164… > Settings > Faults > Local > Web server
Web server
Data point
Explanation, example
M
essage triggering
Default val.: Coming
Setting val:
Coming,
Coming and going
Coming
: A message is triggered when a fault
is received (start of fault).
Coming and going
: A corresponding
message is triggered at start and end of fault.
web server fault displays the LED
A
.
—
Path: Home > 0.5 OZS164… > Settings > Faults > Local > Fault input 1…2
Fault input 1…2
The following settings specify behavior in case of faults.
Select "Settings > Inputs > Fault input 1…2" to configure the fault inputs.
Data point
Explanation, example
F
ault input 1..2*
Default val.: (Blank)
Setting val:
Max. 20 characters
Customizable text for fault input. The
designation is displayed in the menu and
transmitted as part of the message.
Identical to data point in "Settings > Inputs >
ault input 1…2".
F
—
Fault status message
elay
mm:ss
d
Default val.: 00:05.
Setting val:
00:00…59:55
(Resolution
00:05)
The Fault status message delay acts as a
filter for short-term fault events. The time the
web server must wait until a fault becomes
ctive is set here.
a
—
F
ault priority
Default val.: Urgent
Setting val:
Urgent
Not
urgent
Filter when sending a fault.
The setting
Urgent
sends the fault to all active
message recipients. The setting
Not urgent
exempts all message recipients subscribing to
Only urgent ones".
"
—
34 / 108
Siemens Web
server
CE1C5711en
Building Technologies
Commissioning
25.08.2010