Point Database
Siemens Building Technologies, Inc.
4-15
Landis Division
!3K\VLFDOñý9LUWXDOý3RLQWýDGGUHVV
!3K\VLFDOñý9LUWXDOý$872ý3RLQWýDGGUHVV
!3K\VLFDOñý9LUWXDOý)$67ý3RLQWýDGGUHVV
!3K\VLFDOñý9LUWXDOý2))ý3RLQWýDGGUHVV
!3K\VLFDOñý9LUWXDOý21ý2))ý3RLQWýDGGUHVV
!3K\VLFDOñý9LUWXDOý21ý3RLQWýDGGUHVV
!3K\VLFDOñý9LUWXDOý3URRIý3RLQWýDGGUHVV
!3K\VLFDOñý9LUWXDOý6/2:ý3RLQWýDGGUHVV
!3K\VLFDOñý9LUWXDOý6723ý3RLQWýDGGUHVV
Depending on the point being defined, the system will display any of the above prompts after
the field panel has been identified. Each point type has different characteristics, so the
system will display the appropriate prompt for the type being defined.
A
physical
point address means a point is associated to an actual termination in the field
panel. The
virtual
point address means the point resides in memory. If the point serves a
specific purpose (such as a complex digital requiring multiple points to control specific
states), then the system will identify which point (and state) is being defined. The system
does not prompt for the FLN, DROP and POINT numbers when defining virtual points.
!ý)/1
The number of the FLN (floor level network) that the point resides on. If the point resides in
the field panel, the FLN Number is 0. If the point resides in an FLN device, the FLN Number
can be 1, 2, or 3.
NOTE:
Although the Open Processor only resides on FLN 1, it takes up the address
space of FLN 1, 2, and 3.
!ý'URS
A number from 000 to 255 that identifies the Point Termination Module (PTM) or an FLN
device address in which the point resides. If the point resides in the field panel, the Drop
Number is the number of the PTM address key. If the point resides in an FLN device, the
Drop Number is the FLN device number.
!ý3RLQW
A number that identifies the physical point within the field panel or the point on the FLN
device. The valid values for point numbers are set by the actual layout of the hardware within
the field panel or FLN device.
S
S
S
Stttta
a
a
atttte
e
e
e tttte
e
e
ex
x
x
xtttt
The following attribute is used to define state text for digital and LENUM points:
!6WDWHýWH[WýWDEOH
Designates the state text table assigned to a particular point. To use the default entry for a
point, press E
E
E
En
n
n
ntttte
e
e
errrr without typing a number. To assign an alternate state text table, type the
table name and press E
E
E
En
n
n
ntttte
e
e
errrr. If the name of a particular table is unknown, type ?
?
?
? and press
E
E
E
En
n
n
ntttte
e
e
errrr to display a list of available state text tables.