![Siemens NXPLUS C Скачать руководство пользователя страница 251](http://html.mh-extra.com/html/siemens/nxplus-c/nxplus-c_installation-and-operating-instructions-manual_375718251.webp)
802-9081.9 • INSTALLATION AND OPERATING INSTRUCTIONS • NXPLUS C • Revision 11
251/293
Operation
Bus sectionalizer panel with two three-position disconnectors: Earthing the right-
hand busbar system
1
Initial situation
2
➭ Push the interrogation lever downwards and
hold it.
3
➭ Push the right-hand control gate to the left
and hold it (the interrogation lever locks in
lower position. The right-hand actuating
opening for the DISCONNECTING function
opens).
4
➭ Switch the right-hand three-position
disconnector to CLOSED position (insert
the operating lever and turn 90°
clockwise).
5
➭ Remove the operating lever (the interrogation
lever and the control gate return to their initial
position).
6
➭ Push the interrogation lever downwards
again and hold it.
7
➭ Push the left-hand control gate to the
right and hold it (the interrogation lever
locks in lower position. The left-hand
actuating opening for the READY-TO-
EARTH function opens).
8
➭ Switch the left-hand three-position
disconnector to READY-TO-EARTH position
(insert the operating lever and turn 90°
clockwise).
9
➭ Remove the operating lever (the
interrogation lever and the control gate
return to their initial position).
10
➭ To earth the right-hand busbar system,
close the circuit-breaker.
11
➭ Fit a padlock.