NXAirS Withdrawable Metal-enclosed Switchgear, Rated Voltage Up to 12kV
34
Faults
Causes
Measures
Sliding block for feeder
earthing switch cannot
open.
Removable part is in working
position.
Return the removable part to
test position.
Operating handle for removable
part is still inserted in.
Take out the operating handle.
One interlock on control panel is
locked up.
Unlock this interlock according
to normal operation procedures.
Sliding block is locked up by the
padlock.
Open the padlock.
Feeder earthing switch
cannot be closed
(electric failure).
Removable part is in working
position.
Return the removable part to
test position.
Operating handle for removable
part is still inserted in the hole.
Take out the operating handle
for removable part.
One interlock on control panel is
locked up.
Unlock this interlock according
to normal operation procedures.
Without control voltage.
Restore the control voltage.
Feeder earthing switch
cannot be opened (electric
failure).
Without control voltage.
Restore the control voltage.
Operating handle for removable
part is still inserted in the hole.
Take out the operating handle
for removable part.
One interlock on control panel is
locked up.
Unlock this interlock according
to normal operation procedures.
Earthing Switch
Faults
Causes
Measures
Circuit breaker cannot be
closed.
Operating handle for removable
part is still inserted in.
Take out the operating handle
for removable part.
Removable part is in middle
position.
Drive the removable part
to working position or test
position.
Spring is without energy.
Wait for 10 seconds (motor
energy storage) or manual
energy storage.
Undervoltage trip doesn't act.
Force the undervoltage trip to
action.
The door for HV compartment is
not closed.
Close the door for HV
compartment.
Spring without energy.
Without control voltage.
Switch on control voltage or
manual energy storage.
Circuit Breaker
Operation of NXAirS