NXAirS Withdrawable Metal-enclosed Switchgear, Rated Voltage Up to 12kV
5
NXAirS description
NXAirS description
5. Features
NXAirS Switch panel has the following features
●
Factory-assemble, type-test, indoor installation, according to GB3906, IEC62271-200/VDE0671-200 standards.
●
Degree of continuity: LSC 2B
Feature of person Safety
●
All switching operations can only be performed with front door closed
●
Degree of protection: IP4X, according to part 1 of GB4208, IEC60529 and VDE0470
●
Passed the test of internal arcs, according to GB3906\IEC62271-200
●
Degree of PM(Metal)
●
Reliable interlocks protect against accidental contact with live parts
●
Mechanical status indication of circuit-breaker can be recognized through the inspection window, the status of the earthing switch
indicated on the front door.
●
Logical control Interlocks prevent wrong operation
●
Option: Voltage detector. The status in the switchgear panel can be recognized by voltage detection.
●
Earthing status of the feeders can be recognized by auxiliary switch.
Feature of Operation
●
Operations of switch are from the front of the panel
●
The operation handle holes and control units are clearly allocated beside the mechanical indicators
●
There are mechanical indicators of switch on mimic diagram
●
Manual/Motor-driven cassettee and earthing switch
Flexibility
●
Panel can be wall mounted or not.
●
Cable connection can be done from both front and rear of the panel
●
Middle place, withdrawable panel
●
Connection of all normally used types of cables
●
Extension of existing switchgear at both ends without modification of panels
●
Easy to install or remove of bushing-type current transformer from front of the panel
●
Several optional secondary capacity of current transformer
●
Withdrawable parts with same code can interchange completely
●
Easy replacement of compartment by modular bolted construction
●
Busbar voltage sensors are installed in a separate additional compartment with pressure-resident partition to the busbar compartment
●
Every compartment has pressure relief channel
●
Pressure relief upwards for each compartment
●
Pressure-resistant floor cover
●
Control cables are placed in metallic cable ducts
●
With cable testing device, the cable can be tested through the open partition of the switching compartment without switch off the
busbar
Figure 1.
Front view of the switchgear