NXAirS Withdrawable Metal-enclosed Switchgear, Rated Voltage Up to 12kV
9
NXAirS description
7.3 Busbar compartment
●
Construction of rated current
≤
2500A or
>
2500A
●
Busbars made of bare flat copper, bolted from panel to panel
●
Pressure release upwards
●
Insulated busbars
●
Separated comparment
●
Post insulator with capacitive division
●
Natural ventilation
●
Pressure switch
7.4 Cable connection compartment
●
Construction of rated normal current 630A~4000A
●
Panel bars made of bare copper
●
Pressure release upwards through a separate duct
●
Single-core XLPE up to max.4×500mm
2
●
Busbars: with insulating bushing ( optional )
●
Block-type CT: Max. 3, (1 CT with 1or 2 coils) made of epoxy resin.
●
PT can be installed optionally, max.3
●
Arresters or over-voltage protection device
●
HV HRC fuses in metering module
●
Make-proof earthing switch
●
Cable-type CT at the bottom of the connection compartment
●
Natural ventilation (current above 2500A)
●
Heating device
●
Motor-driven earthing switch
7.5 Low-voltage compartment
●
Completely separated from the other compartments, and removable
●
For installation of protection, control, measuring and metering equipment
●
Plug is adapted to connection of conductor and control cable
●
705 mm is the standard height
●
Open the door from left
●
partition between low-voltage compartment and high-voltage compartment
●
Illumination
●
Heating device
●
The optional height is 980mm
7.6 Additional compartment to the busbar compartment (optional)
●
An independent partitioned additional compartment, bolted to the busbar compartment
●
Isolation partition between additional compartment and busbar compartment, install PT with single pole, max. 3.
●
Separate pressure release for the additional compartment
●
Busbar upward connection
Basic features
Option
Option
Basic features
Cables
Option
Basic features
Basic features
Option