Introduction
2
Interactions
12
Building Technologies
A6V10062437_a_en
Fire Safety & Security Products
30.06.2013
2.1
Interactions
The unit can be programmed to support interactions between the connected
subsystems: when a specified message is received from a source subsystem, one or
more commands are generated for a destination subsystem according to the
programmed interaction logic.
Interactions can be
local or network-wide:
Local interactions only involve the subsystems connected to a single unit.
Network-wide interactions involve subsystems connected on different units, which
coordinate the interaction task over the network. Network-wide interactions require
units supporting the BACnet protocol.
Note: NK8000 units are not certified as part of an EN54-2 fire detection system.
Therefore, the interactions should only be used in applications where they are not in
conflict with EN54 standards or national guidelines or regulations (e.g. not for
common control of remote transmission devices).
Note: NK8231 and NK8237 do not support interactions.
Both local and network-wide interactions are supported for a restricted list of
subsystems:
FS20 Sinteso Fire control units (this subsystem is not supported by NK822x)
FS720 Cerberus Pro Fire control units (this subsystem is not supported by
NK822x)
STT20 Fire control unit (this subsystem is not supported by NK822x)
CS11 AlgoRex
®
Fire control unit
CS1115 Fire control unit
FC330A Fire control unit
FC700A Fire control unit
SIGMASYS/D100 Fire control unit
XLS FireFinder control unit
CS6 Guarto Intrusion control unit
SI410 Intrunet (formerly Sintony) Intrusion control unit
DF8000/CF9000 I/O modules
MK7022 Cerloop Interface
Philips Burle CCTV switcher
For details on interactions, see the
Network Connectivity Guide (document
no.A6V10359485).