CM AS Interface, communication states
The CM AS Interface has three communication states: The LED is lit green, red or flashes
red/yellow.
LED AS-I is lit
Green
Red
Red/Yellow
AS Interface communication OK AS Interface communication
failed
Slave has address "0".
CM AS Interface, behavior on communication failure
●
If the AS Interface voltage fails, communication between the LOGO! system and the
expansion modules, which are arranged to the right of the LOGO! CM AS Interface
expansion module, is interrupted.
Recommendation: Position LOGO! CM AS Interface on the far right side.
●
If communication is interrupted, the switching outputs are reset after about 40 to 100 ms.
CM EIB/KNX, communication states
The CM EIB/KNX has three communication states: The LED is lit green, red or orange.
LED BUS is lit
Green
Red
Orange
Bus connection OK,
communication OK,
no programming mode
Bus connection interrupted
Programming mode active and
bus connection OK
CM EIB/KNX, behavior on communication failure
●
LOGO! voltage failure
If there is a power failure of LOGO! or a disruption in the communication to the LOGO!
master or to the communication partner on the left side, the outputs are set to 0. The
RUN/STOP LED lights up red after a second.
●
LOGO! voltage recovery
LOGO! starts up again, CM EIB/KNX sends the parameterized states.
●
CM EIB/KNX voltage failure
All the inputs of the LOGO! master on the
EIB are set to 0 by the LOGO! master.
●
CM EIB/KNX voltage recovery
All the outputs of the LOGO! master on the
EIB are updated. The inputs are read by the
EIB depending on the parameterization.
●
Short circuit on the bus or bus interruption
The behavior can be parameterized in the LOGO! configuration window of the application
program in ETS (EIB Tool Software). The red light is set after 5 seconds.
●
Bus recovery
The behavior can be parameterized in the LOGO! configuration window.
Содержание LOGO!
Страница 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Страница 136: ...Programming LOGO 3 9 Memory space and circuit program size LOGO 136 Manual 04 2011 A5E03556174 01 ...
Страница 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Страница 302: ...Configuring LOGO 7 2 Setting the default values for LOGO LOGO 302 Manual 04 2011 A5E03556174 01 ...
Страница 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Страница 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Страница 400: ...Safety instructions 2 3 Notes about usage Basic Panels 28 Operating Instructions 04 2012 A5E02421799 03 ...
Страница 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...