![Siemens LOGO! Скачать руководство пользователя страница 330](http://html.mh-extra.com/html/siemens/logo/logo_manual_377208330.webp)
Technical data
A.6 Technical data: LOGO! 24RC...
LOGO!
330
Manual, 04/2011, A5E03556174-01
A.6
Technical data: LOGO! 24RC...
LOGO! 24RC
LOGO! 24RCo
Power supply
Input voltage
24 V AC/DC
Permissible range
20.4 ... 26.4 V AC
20.4 ... 28.8 V DC
Reverse polarity protection
- -
Permissible mains frequency
47 ... 63 Hz
Power consumption
•
24 V AC
•
24 V DC
•
45 ... 130 mA
•
40 ... 100 mA
Voltage failure buffering
typ. 5 ms
Power loss
•
24 V AC
•
24 V DC
•
1.1... 3.1 W
•
1.0 ... 2.4 W
Backup of the real-time clock at 25 °C
typ. 80 hours without battery card
typ. 2 years with battery card
Accuracy of the real-time clock
typ. ± 2 s / day
Digital inputs
Number
8,
optional P action or N action
Electrical isolation
No
Number of high speed inputs
0
Input frequency
•
Normal input
•
High speed input
•
max. 4 Hz
•
- -
Max. continuous permissible voltage
26.4 V AC
28.8 V DC
Input voltage
•
Signal 0
•
Signal 1
L
•
< 5 V AC/DC
•
> 12 V AC/DC
Input current at
•
Signal 0
•
Signal 1
•
< 1.0 mA
•
> 2.5 mA
Delay time at
•
0 to 1
•
1 to 0
•
typ. 1.5 ms
•
typ. 15 ms
Line length (unshielded)
max. 100 m
Analog inputs
Number
- -
Содержание LOGO!
Страница 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Страница 136: ...Programming LOGO 3 9 Memory space and circuit program size LOGO 136 Manual 04 2011 A5E03556174 01 ...
Страница 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Страница 302: ...Configuring LOGO 7 2 Setting the default values for LOGO LOGO 302 Manual 04 2011 A5E03556174 01 ...
Страница 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Страница 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Страница 400: ...Safety instructions 2 3 Notes about usage Basic Panels 28 Operating Instructions 04 2012 A5E02421799 03 ...
Страница 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...