LOGO! functions
4.4 Special functions list - SF
LOGO!
208
Manual, 04/2011, A5E03556174-01
Limit value of OT
The value of the operating hours in OT is retained when you reset the hours counter with a
signal at input R. The hours counter OT will be reset to zero with a transition from 0 to 1 at
Ral. The hours counter OT continues the count as long as En = 1, irrespective of the status
at the reset input R. The counter limit of OT is 99999 h. The hours counter stops when it
reaches this value.
In programming mode, you can set the initial value of OT. MN is calculated according to the
following formula when reset input R is never enabled: MN = MI - (OT % MI). The % operator
provides an integer division remainder.
Example:
MI = 30h, OT = 100h
MN = 30 - (100 % 30)
MN = 30 -10
MN = 20h
MN
OT
30h
30h
30h
30h
20h
100h
MI
0
20
40
60
80
100
120
In runtime mode, the value OT can not be preset. If the value for MI is changed, there would
be no calculation for the MN. MN would take on the value of MI.
Setting the Par parameter
View in programming mode:
P
0, K
%5
0,ൺ%K
%5
P
27 K
%5
4ൺ5(Q
%5
MI is the configurable time interval. The permissible range of values is 0 to 9999 hours.
Содержание LOGO!
Страница 8: ...Preface LOGO 8 Manual 04 2011 A5E03556174 01 ...
Страница 136: ...Programming LOGO 3 9 Memory space and circuit program size LOGO 136 Manual 04 2011 A5E03556174 01 ...
Страница 278: ...LOGO functions 4 4 Special functions list SF LOGO 278 Manual 04 2011 A5E03556174 01 ...
Страница 302: ...Configuring LOGO 7 2 Setting the default values for LOGO LOGO 302 Manual 04 2011 A5E03556174 01 ...
Страница 366: ...Abbreviations LOGO 366 Manual 04 2011 A5E03556174 01 ...
Страница 372: ...Index LOGO 372 Manual 04 2011 A5E03556174 01 ...
Страница 400: ...Safety instructions 2 3 Notes about usage Basic Panels 28 Operating Instructions 04 2012 A5E02421799 03 ...
Страница 534: ...Index Basic Panels 162 Operating Instructions 04 2012 A5E02421799 03 ...