31/44
Siemens
Rotary actuators without spring return GBB/GIB..1
CE1Z4626en
Smart Infrastructure
Commissioning notes
2019-11-28
Set address “5”:
1. Enter addressing mode
2. Set 1- digit: Press button 5-times
→
LED flashes
green
per button press
Store address: press button until LED shines
red
→
address is stored and displayed 1x for confirmation
7.3.3 Commissioning
The devices are especially designed for using the Climatix push-button configuration as
described in document A3975
1)
. The bus configuration can alternatively be
parameterized by the local HMI, cf. page 29.
During commissioning check/set the following:
·
Bus configuration (address, baudrate, transmission mode, and optionally
termination). The default address 255 allows to mount and power multiple actuators
at the same time without interfering with each other.
·
Damper actuator parameters (opening direction, position limits, position adaptation
etc.) can be checked via the Modbus register.
1)
The documents can be downloaded from
http://siemens.com/bt/download
The devices can be configured over bus if the pre-commissioning settings allow for a
connection between the Modbus master / programming tool and peripheral devices (i.e.
non-conflicting addresses and matching baudrate / transmission format).
·
Full configuration over bus: If the address is unique per segment when powered up,
the device can be accessed by the Modbus master (or programming tool) and the
address and other parameters can then be set to the definitive values.
·
Partial configuration over bus: If the address is not unique per segment when
powered up, each device must get a non-conflicting address before connecting it to
the bus, either by using the address input with push button (cf. page 30 ) or by
setting the address to 246 with push button press > 5s und < 10s (cf. page 29). After
addressing all devices, the remaining configuration can be done over the bus using
the default settings for baudrate (auto-baud) and transmission mode for the Modbus
master.
·
Overwriting the bus configuration over bus uses a timeout. If „1 = Load“ is not written
into Reg 768 within 30 seconds, all values are discarded.
Example: Table shows bus configuration registers before and after changing them over
bus.
Reg.
Name
Pre-commissioning
New value (ex.)
764
Modbus Address
246
12
765
Baudrate
0 = auto
1 = 9600
766
Transmission Format
0 = 1-8-E-1
3 = 1-8-N-2
767
Termination
0 = Off
0 = Off
768
Bus Conf. Command
0 = Ready
1 = Load
Workflow 1
Workflow 2