35/44
Siemens
Rotary actuators without spring return GBB/GIB..1
CE1Z4626en
Smart Infrastructure
Technical data
2019-11-28
8
Technical data
Operating voltage
Frequency
Safety extra-low voltage (SELV) or
Protective extra-low voltage (PELV) as per
Requirements for external safety isolating transformer (100 % duty)
Supply line fuse
Power consumption GBB/GIB13..1: Running
GBB16.1/GIB16..1..: Running
GBB/GIB16..1: Holding
AC 24 V
±
20 %
or AC 24 V class 2 (US)
50/60 Hz
HD 384
as per EN 61 558
max. 10 A
7 VA, 7 W
8 VA, 8 W
1.1 W
Operating voltage
Frequency
Supply line fuse
Power consumption: GBB/GIB33..1: Running
AC 230 V
±
10 %
50/60 Hz
max. 10 A
5 VA, 5 W
Nominal torque
Maximum torque (blocked)
Nominal rotary angle / max. rotary angle
Runtime for 90° rotary angle
Mechanical life
25 Nm GBB
35 Nm GIB
50 Nm GBB
75 Nm GIB
90 ° / 95° ± 2°
150 s (50 Hz) / 125 s (60 Hz)
10
5
cycles
Operating voltage AC 24 V
(wires 1-6)
clockwise
(wires 1-7)
Counter-clockwise
Operating voltage AC 230 V (wires 4-6)
clockwise
(wires 4-7)
Counter-clockwise
Input voltage (wires 8-2)
Current consumption
Input resistance
Max. permissible input voltage
Protected against faulty wiring
Neutral zone for nonadjustable characteristic function
for adjustable characteristic function
Hysteresis
for nonadjustable characteristic function
for adjustable characteristic function
DC 0...10 V
0.1 mA
> 100 k
W
DC 35 V
max. AC 24 V
200 mV
2 % of
D
U
70 mV
0.7 % of
D
U
Communication
Modbus RTU
RS-485, not galvanically separated
Number of nodes
Max. 32
Address range
1...247 / 255
Default: 255
Transmission formats
1-8-E-1 / 1-8-O-1 / 1-8-N-1 / 1-8-N-2
Default: 1-8-E-1
Baudrates (kBaud)
Auto / 9.6 / 19.2 / 38.4 / 57.6 / 76.8 /
115.2
Default: Auto
Termination
120
Ω
el. Switchable
Default: Off
Adjustable with 2 potentiometers:
Offset Uo
Span
D
U
Max. input voltage
Protected against faulty wiring
DC 0...5 V
DC 2...30 V
DC 35 V
max. AC 24 V
Output signal (wires 9-2)
Output voltage U
Max. output current
Protected against faulty wiring
DC 0...10 V
DC
±
1 mA
max. AC 24 V
Change of resistance (wires P1-P2)
Load
Max. sliding contact current
0...1000
W
< 1 W
< 10 mA
AC 24 V supply
(SELV/PELV)
AC 230 V power supply
Functional data
Inputs
Positioning signal
for GBB/GIB13..1
Positioning signal
for GBB/GIB33..1
Positioning signal
for GBB16..1/GIB16..1..
Adjustable characteristic function
for GBB/GIB163.1,
GBB/GIB164.1
Outputs
Position indicator
for GBB/GIB16..1
Feedback potentiometer
for GBB/GIB135.1,
GBB/GIB335.1