28/44
Siemens
Rotary actuators without spring return GBB/GIB..1
CE1Z4626en
Smart Infrastructure
Commissioning notes
2019-11-28
Check of output voltage U:
·
U = DC 0...10 V for
angular rotation 90°
.
Measures resistance changes while the actuator turns from 0 to 90°.
·
Switchover of the auxiliary switch contacts "A" and "B" as soon as the actuator
reaches the respective switching positions.
·
Set the setting shafts (part of the delivery) to the desired value by means of a
screwdriver (see section 3.2 "Angular range and mechanical limitation”).
The angle values are valid only for the
zero
position of the actuator (clockwise
direction).
The auxiliary switches have the following factory settings:
·
Switch A: Switchover point at 5°
·
Switch B: Switchover point at 85°
46
26
Z02
The set direction of rotation must agree with the required
direction of rotation of the air damper..
Factory setting:
For the special diagrams according to section 9.4.2, the
operating states must also be checked.
Position indicator
Feedback potentiometer
Auxiliary switches
A and B
Important
Factory setting
Rotary direction switch
for GBB/GIB16..1