Operation
5
Testing
135
Building Technologies
A6V10380629_en--_a
Fire Safety
2015-09-10
a
The highlighted list entry is displayed with a bright background.
7. Press 'Execute commands' on the dialog window toolbar.
a
The 'Select command' dialog window opens.
8. Select the 'Non-MCP zones det.test' command.
a
All automatic 'Detectors' are set to 'Detector test'.
a
The 'DETECTOR TEST' LED on the Person Machine Interface is on.
a
The command execution display confirms successful execution of the
command by displaying
.
9. Test the 'Detectors'.