Operation
5
Switching off / Switching on
117
Building Technologies
A6V10380629_en--_a
Fire Safety
2015-09-10
5.3.4 Switching off / on the remote transmission Fire
WARNING
When the remote transmission Fire has been switched off, the fire brigade cannot
be called up in the event of fire!
Fire may spread unhindered.
● Deploy staff to monitor the ↑ 'Site'.
● You must switch the 'RT Fire' back on as soon as possible.
The 'RT Fire' is normally switched on and may only be switched off in particular
cases, e.g. for a function check of controls.
Remote transmission, fire can be switched off in the following two ways. Both ways
are then shown.
l
Switch off 'RT Fire' via the 'Topology' dialog window.
l
Switch off 'RT Fire' via the 'Functions' menu item.
Switch off 'RT Fire' via the 'Topology' dialog window
w
You are logged onto at least 'Access level' 2.1.
1. Press the button 'Topology' on the GTB.
a
The 'Topology' dialog window opens.
2. Press 'Lower level' in the 'Control tree' list entry.
a
All 'Stations' in the 'Control tree' are displayed.
3. Press 'Lower level' in an 'Station' list entry.
a
All elements of the 'Station' are displayed.
4. Highlight the list entry 'Alarmg. 1'.
a
The highlighted list entry is displayed with a bright background.
5. Press 'Execute commands' on the dialog window toolbar.
a
The 'Select command' dialog window opens.