Operation
5
Activation / Deactivation / Reset
127
Building Technologies
A6V10380629_en--_a
Fire Safety
2015-09-10
a
All 'Areas' in the 'Detection tree' are displayed.
2. Press 'Lower level' in an 'Area' list entry.
a
All 'Sections' in this 'Area' are displayed.
3. Press 'Lower level' in an 'Section' list entry.
a
All 'Zones' in this 'Section' are displayed.
4. Highlight a 'Zone'.
a
The highlighted list entry is displayed with a bright background.
5. Press 'Execute commands' on the dialog window toolbar.
a
The 'Select command' dialog window opens.
6. Select the 'Activate' command.
a
The command execution display confirms successful execution of the
command by displaying
.
a
The 'Zone' is activated.
Reset 'Zone'
1. Press <Reset>.
a
The 'Login/logout' window is open.
2. Enter an admissible PIN.
a
'Zone' is reset.