OPERATION
3-3
CHAPTER 3
|
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
AUDIBLES - Audibles ON or Audibles SILENCED glows steady yellow.
PARTIAL SYSTEM DISABLED - Partial System Disabled glows steady yellow
when any module/device is disabled or the system is in walktest.
CPU FAIL (PMI-2/PMI-3 only) - CPU Fail glows steady yellow when a main
processor failure occurs in the PMI-2.
q
Press
....
(PMI) or
MENU
(PMI-2/PMI-3) to display a MENU of available information.
r
Scroll UP / Scroll DOWN - Use the scroll up button to navigate up or the scroll
down button to navigate down a list to choose a specific entry from the list of
information displayed on the screen. If the button remains depressed, the list
scrolls progressively faster until it reaches ten items at a time.
s
MORE INFO + - Use
More Info/+
to navigate or drill down through the levels of
detail about a selected entry. When viewing a report that is longer than one
screen, pressing (+) highlights the first entry of the report.
MORE INFO—(PMI) or
(PMI-2) - Use
More Info/-
or
ESC
to navigate or drill up
through the levels of detail about a selected entry. When viewing a report that is
longer than one screen, pressing — or ESC highlights the last entry of the report.
t
HELP - Press
?
for context-sensitive help. Press
?
again or press the Exit Help
soft key to return to your previous position. If no key presses are made for 60
seconds, the help will time out and return to the previous screen.
u
Touch screen display - Touch selections on the screen when there are options
that are not selectable using the soft keys. Use of the touch screen is not
required in Alert mode.
The model PMI-2 and PMI-3 are direct replacements for the model PMI, therefore in
the screens that display system information, the model name PMI represents the
PMI, PMI-2, and PMI-3.
NORMAL MODE
Normal mode is the absence of any event conditions.
The screen displays SYSTEM
STATUS: NORMAL with the time
and date. If a custom message has
been programmed using the Zeus
tool (refer to Zeus Quick Start
Guide, P/N 315-033875), the node
custom message also displays in this
mode. See Figure 3-4.
The POWER LED glows steady
green in Normal mode when
the System has AC power. The
ALARM, AUDIBLE ON, AUDIBLE
SILENCE, SUPERVISORY,
TROUBLE, SECURITY (PMI/PMI-2
only), and PARTIAL SYSTEM DISABLE
LEDs are off and the internal audible is off.
CUSTOM MESSAGE
FireFinder - XLS System
10:26:12 07/12/02
SYSTEM STATUS: NORMAL
Figure 3-4
Normal Mode Display