GLOBAL VOICE
5-23
CHAPTER 5
|
FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Global Command Station 1
Global Request
Global Grant
Global Deny
Local Command Station
Global Request
Global Grant
Global Deny
Global Command Station 2
Global Request
Global Grant
Global Deny
Note that all 3 command stations regardless of node location
or type (local or global) share the same set of Global Request /
Global Grant / Global Deny switches. Access must be granted
for any action to be performed (local or global).
Figure 5-2
Global Access Control Concept
Lamp Test
Lamp Test allows the user to test all visible terminal indications.
To perform a Lamp Test, follow the steps listed below.
1.
Depress the Lamp Test switch.
2.
All LEDs will be on steady red, then steady green followed by steady
yellow, each for approximately 3 seconds.
3.
The Lamp Test automatically shuts off after cycling through the LED colors.
Clear Manual and
Clear Manual allows the user to cancel all manually activated functions with a single
switch press.
1.
Clear Manual only removes manual activations from the local node.
2.
Global Clear Manual removes all manual activations from all nodes in the
system.
To clear all manually activated functions, follow the steps listed below.
1.
Depress the Clear Manual switch.
2.
The Emergency Page, Evacuation, Alert, Convenience Page and Background
Music will be canceled.
3.
All activated LEDs turn off.
Global Clear Manual