Operation
Operations under access level 2
8
A6V10421795_en--_k
83 | 151
3. Select 'Event log' and press
. The 'Event log' window is open.
Event log L2
1 - Show log
2 - Advanced
4. Select 'Advanced' and press
. The 'Advanced' window is open.
Advanced L2
Type: All
Start time: 08-01-2015
End time: 08-01-2015
Print:
✕
Query
5. Select 'Type:', enter 'Start time:'/'End time:', and then select 'Query' and press
. All filtered events are displayed. Scroll by using
/
.
Rec. 001 of 008 L2
+ Short
Monitored output
Output card 4M
Circuit 02
03-01-2020 18:08:08
Explanation to number on the top line 'Record XXX of YYY':
XXX: Serial number of event, the first event is '001', the last event is 'YYY'.
YYY: Total number of all events.
For detailed information about the LCD display, see '
To print filtered events, select 'Print:
' with '√' in step 4.
8.5.3.2 Viewing compensation values
A compensation value in compensation logs/reports indicates dirt/dust level in
chamber of smoke detector OP720, OH720, OOH740, OOHC740, OP360 or
OH360. If it becomes larger, it means:
● The detector chamber is dirtier.
● The band of detection range is smaller.
● The possibility of initiating false fire detection is higher.
In order to avoid false fire detection due to chamber dust level, note the following
compensation value range: