Installation
Inputs/outputs
6
A6V10421795_en--_k
41 | 151
6.8 Inputs/outputs
The panel mainboard has four configurable inputs/outputs. Each one can be
configured as an input or output.
The default settings are:
● IO1/IO2: input
● IO3/IO4: output
Fig. 12: Connection of configurable IOs
1 Configured as input (Connect to '0V' and IO)
2 Configured as output (Connect to '24V' and IO)
Configured as 'input'
The inputs can be triggered by a potential-free contact. They can be configured as
one of the following usages:
● Class Change Usage
● Evacuation usage
● Reset command
● Access level 2
● Disable RT Fire and RT Fault devices
● Activate manned
● Toggle between manned/ unmanned
● Initiate extra PSU fault
● Dialer (RT Fire Device) Fault
● Initiate fire brigade is called
● Acknowledge command
● Voice test Usage
● Door holder off
See document
for detailed description of each usage.
Configured as 'output'
Configuration as 'output' allows the activation of external devices (e.g. relays) with
24 V voltage.
The line is not monitored.
Содержание FC361 Series
Страница 6: ......