Operation
Operations under access level 2
8
80 | 151
A6V10421795_en--_k
8.5.2.3 Voice test
This function checks if voice alarm devices play the voice test message (M4) in a
specific language order defined under task card ‘Site’ in 'FC360 Panel
Configurator'.
You can activate/deactivate voice test locally in the fire control panel via menu
operation, or remotely in the configuration tool via input modules, I/O modules or
digital inputs on the mainboard IO (see document
If you want to deactivate voice test after you’ve activated it, the audio doesn’t stop
at once unless the voice test sequence is completed. However, if a real fire event
occurs during a voice test, the message with a higher priority is played
automatically.
To activate/deactivate voice test in the fire control panel
1. Press
on the keypad. The 'Main menu' window is open.
Main menu L2
1 - System status
2 - Operation
3 - Event memory
4 - Login
5 - Lamp test
7 - Logout
2. Select 'Operation' and press
. The 'Operation' window is open.
Operation L2
1 - Isolation
2 - Test
3. Select 'Test' and press
. The 'Test' window is open.
Test L2
1 - Detection
2 - Lamp test
3 - Voice test
4. Select 'Voice test' and press
. The 'Voice test' window is open.
Test - Voice test L2
1 - Voice test (ON)
2 - Voice test (OFF)
5. Select '1 - Voice test (ON) ' and press
to activate voice test, or select '2 -
Voice test (OFF)' and press
to deactivate voice test.