70
OFF
There is no Ground Fault event in system.
Flashing
There are ground fault events in system, but
some of them have not been acknowledged.
7
Audible
On (US)
Alarm
Signal
Activation
(Canada)
Red
Steady ON
The LED 7 can only be steady on when any of
the following conditions are met:
1. There are activated NACs and some of
them are not silenced.
2. There are silenceable devices activated
and some of them are not silenced.
OFF
The LED 7 will be OFF when above conditions
are not met.
The buzzer operates as follows:
Normally OFF
–
indicates that the system is in normal condition or all events in the system
have been acknowledged.
ON (200 pulse per minute)
–
indicates that at least ONE unacknowledged alarm is present in
the system.
ON (85 pulse per minute)
–
indicates that at least ONE unacknowledged non-alarm (trouble,
supervisory) event is present in the system.
The buttons operates as follows:
Item
Button
Action
Description
8
Programmable (US)
Press
Press button 8 to execute user defined and configured
functions.
Alarm Signal Activation
(Canada)
Press button 8 to report the alarm zone events to the
panel.
9
Silence/Unsilence (US)
Press
The button toggles between silence and unsilence. Press
button 9 to silence the audible and/or visual notification
appliances (where permitted by the codes and control
panel programming). The notification appliances will be
de-activated, and the LED 3 will be off. Press button 9
again to unsilence the previously silenced notification
appliances.
Signal Silence/Unsilence
(Canada)
10
Acknowledge/Buzzer
Silence
Press
Acknowledges unacknowledged events in system.
17
Reset
Press
Clears all obsolete events and resets all devices, except
those disabled ones and hold-through-reset devices in
system.
11
C
Press
Cancel button for PMI operation.
12
OK
Press
OK button for PMI operation.
13
*
Press
* button for PMI operation.
14
#
Press
# button for PMI operation.
15
0-9
Press
Numeric buttons for PMI operation. They are used to
enter the password to access the maintenance and
technician modes of the panel. It allows the user to
program the panel using these keypads without using the
firealarmresources.com
Содержание FC2005
Страница 5: ...firealarmresources com ...
Страница 33: ...28 FC2005 Enclosure Mounting Pictures firealarmresources com ...
Страница 48: ...43 firealarmresources com ...
Страница 58: ...53 This page is left intentionally blank firealarmresources com ...
Страница 89: ...84 LE4010 CF Configuration Reference from DSC Installation Manual firealarmresources com ...
Страница 90: ...85 TL300 CF Configuration Reference from DSC Installation Manual firealarmresources com ...