A 26 V (nominal) power supply provides all operating power to the control panel for both
standby and alarm conditions. Batteries no smaller than 12 AH and no greater than 19 AH for
US, and no smaller than 12 AH for Canada must be used to meet code requirements. Sealed
lead-acid batteries within this range have sufficient charging capability to provide 24 hours of
normal standby operation plus 5 minutes of alarm operation for US installations and 30
minutes of alarm operation for Canadian installations.
The battery will be automatically
disconnected at low battery voltage to prevent deep discharge and battery damage.
Signaling Line Circuit (SLC)
The FC2005 fire alarm control panel provides a signaling line circuit with the capacity of 50
addressable devices.
Notification Appliance Circuits
The FC2005 control panel has two independent notification appliance circuit (NACs). It can be
configured as two Class B NACs or one Class A NAC. Each circuit can be selected to give
continuous output or one of five sounding patterns. There is also a system coder capable of
zone operation. All of the NACs are power limited and support synchronization of listed
devices using the Siemens sync protocol.
Serial Interface Circuit (UFP)
The FC2005 control panel has a Serial Interface Circuit that can connect up to 8 devices, e.g.:
remote LCD annunciators, LED driver/tabular annunciator or remote printer module.
Status Relays
Four relays with dry contacts are provided. Three relays are dedicated to alarm, supervisory,
and trouble conditions on the panel. The remaining relay is programmable. The relay contacts
are Form C and are rated for 2 A @ 30 VDC resistive.
Programming Port
A USB standard type B plug is provided for temporary connection to a computer for panel
programming and firmware download when using the FXS901-U2 System Configuration Tool.
DACT
The Digital Alarm Communication Transmitter (DACT) is integrated on the FC2005 main board
and it will send control panel status information to a central or remote receiving station through
the Public Switched Telephone Network (PSTN).
Programmable Key
Press the programmable key to execute the user defined and configured functions. Supported
functions are: DACT bypass, Addressable device bypass, NAC bypass, Fire drill, Manual
evacuation, Co test and Lamp test.
OPTIONAL MODULES
City Tie Module (FCI2020-U1)
The city tie module provides local energy and polarity reversal connections. The polarity
reversal connections provide a trouble circuit and an alarm circuit with optional trouble output.
The city tie board mounts onto the main board.
firealarmresources.com
Содержание FC2005
Страница 5: ...firealarmresources com ...
Страница 33: ...28 FC2005 Enclosure Mounting Pictures firealarmresources com ...
Страница 48: ...43 firealarmresources com ...
Страница 58: ...53 This page is left intentionally blank firealarmresources com ...
Страница 89: ...84 LE4010 CF Configuration Reference from DSC Installation Manual firealarmresources com ...
Страница 90: ...85 TL300 CF Configuration Reference from DSC Installation Manual firealarmresources com ...