NAC Wiring
Two individual NACs are provided and the polarity shown is when the NAC is activated.
Power Limited
Supervised
Current Draw
Maximum Line Resistance
2.5 A
3.2
Ω
2.0 A
4.0
Ω
1.5 A
5.3
Ω
1.0 A
8.0
Ω
0.5 A
16.0
Ω
Alarm voltage: 16 to 32 VDC
Maximum ripple: 0.1 VAC
Used for special application only
Two Class B or one Class A
Total maximum current: 2.5 A
Refer to Desigo_NACs_A6V10333530_c_en to determine synchronized notification appliances
allowed per NAC
Class B
Supervised
Power Limited
See Appendix B for compatible devices
EOL available in the package as part of accessory
24K 0.5W
resistor*
…
..
N_AN
N_AP
N_BN
NAC
N_BP
Same as above
Class A
Supervised
Power Limited
See Appendix B for compatible devices
No EOL devices