45
SLC Addressable Device Circuit
These devices are polled by the control panel every few seconds and input or output functions
communicated to determine device status or function. The control panel monitors all device
addresses for alarm and trouble conditions.
Addressable Device Circuit
Class B (DCLB) or Class A (DCLA) or Class X (DCLC) Operation
Max. 50 devices can be connected to the circuit.
Wire Resistance
–
Max. 50 Ohm
(See Appendix A, Line Resistance Graph)
Supervised, Power Limited
See Appendix B for Compatible Devices
S_AN
S_AP
S_BN
P2 addressable device
S_BP
Addressable device
EARTH
EARTH
firealarmresources.com