Commissioning and diagnostics
ECOFAST Motor Starters
4-6
GWA 4NEB 950 0562-12
4.3
Diagnostics through LED indicators
Table 4-5: Diagnostics through LED indicators
LED
Description
SF
red
General/peripheral fault, e.g. tripping
—> motor tripped
General warning,
see Note below
.
—> motor not tripped
off
No fault
AS-i
red
No data traffic
red-yellow
flashing
Zero address
green
Communication and unswitched supply ok
off
No unswitched supply voltage
green
Unswitched supply voltage ok
off
Unswitched supply voltage not ok
AUX PWR
green
Switched supply voltage ok
off
Switched supply voltage not ok
STATE
green
Circuit state: switching element ON by control /HMI
off
Switching element OFF
red
Circuit state
switching command
IN.1
green
Digital input 1: 24 V DC present
off
Digital input 1: 24 V DC not present
IN.2
green
Digital input 2: 24 V DC present
off
Digital input 2: 24 VDC not present
¬
=
Содержание ECOFAST
Страница 1: ...Part ofTotally Integrated Automation ecofast 02 2002 Motor Starter ...
Страница 7: ...ECOFAST Motor Starters iv GWA 4NEB 950 0562 12 ...
Страница 9: ...ECOFAST Motor Starters vi GWA 4NEB 950 0562 12 ...
Страница 17: ...Motor Starters Overview ECOFAST Motor Starters 1 6 GWA 4NEB 950 0562 12 ...
Страница 25: ...Installation of Motor Starters ECOFAST Motor Starters 2 8 GWA 4NEB 950 0562 12 ...
Страница 55: ...Device functions ECOFAST Motor Starters 5 6 GWA 4NEB 950 0562 12 ...
Страница 63: ...ECOFAST Motor Starters B 2 GWA 4NEB 950 0562 12 B 1 Motor Starter Fig 2 1 Motor starter dimension drawing ...
Страница 75: ...ECOFAST Motor Starter Index 2 GWA 4NEB 950 0562 12 ...
Страница 77: ...Correction page ECOFAST Motor Starters GWA 4NEB 950 0562 12 ...