background image

Wiring and interfaces

ECOFAST Motor Starters

3-16

GWA 4NEB 950 0562-12

3.8

Addressing socket

Definition

The addressing socket is used for addressing with a device such as the 
addressing and diagnostic unit. This is connected to the addressing socket 
with the connecting lead.

 

Fig. 3-11: Addressing socket

Addressing socket

Connecting lead

Screw cap

SF

AS-i

AUX PWR

STATE

IN.1/2

IN.2

ADDR.

DEVICE

X1

X3

Addressing socket

Содержание ECOFAST

Страница 1: ...Part ofTotally Integrated Automation ecofast 02 2002 Motor Starter ...

Страница 2: ...ts Product overview 1 Installation of motor starters 2 Wiring and interfaces 3 Commissioning and diagnostics 4 Device functions 5 Technical data A Dimension drawings B Order numbers C Edition 01 ECOFAST Motor Starters Manual GWA 4NEB 950 0562 12 ...

Страница 3: ...ended by Siemens This product can only function correctly and safely if it is transported stored set up and installed correctly and operated and maintained as recommended Brands SIMATIC SIMATIC HMI ECOFAST and SIMATIC NET are brands of SIEMENS AG Han Brid Han Q8 Han 10E are brands of Harting company Some other designations used in these documents are also brands the owner s rights may be violated ...

Страница 4: ...etup with motor nearby 2 5 2 3 1 Required components 2 5 2 3 2 Installation 2 6 3 Wiring and interfaces 3 1 3 1 Power Cables Prefabricated at One End 3 3 3 1 1 Power Cables Prefabricated at One End with Han Q8 Pin 3 3 3 1 2 Power Cables Prefabricated at One End with Han 10E Pin 3 4 3 2 Wiring rules 3 5 3 2 1 Selecting the power leads 3 5 3 2 2 Unused connections 3 6 3 3 Motor terminal 3 7 3 3 1 Pi...

Страница 5: ...ical switching technology 5 5 A Technical data A 1 A 1 General technical data A 2 A 2 Auxiliary power A 3 A 3 Digital inputs A 3 A 4 Main power A 4 A 4 1 Mechanical switching A 5 A 4 2 Brake output 400 V AC A 6 B Dimension drawings B 1 B 1 Motor Starter B 2 C Order numbers C 1 C 1 Motor Starters Reversing starters C 2 C 2 Motor Connection Cables and Power Cables C 3 C 3 Power Control Modules Infee...

Страница 6: ...er cables prefabricated at one end with Han 10E pin 3 4 Fig 3 4 Pin assignment for motor terminal 3 7 Fig 3 5 Pin assignment for power terminal 3 9 Fig 3 6 Han Q8 power connector 3 11 Fig 3 7 Pin assignment for power tee connector 3 12 Fig 3 8 Pin assignment with circuit examples 3 13 Fig 3 9 AS i interface 3 14 Fig 3 10 Contacting the AS i cables 3 14 Fig 3 11 Addressing socket 3 16 Fig 4 1 Start...

Страница 7: ...ECOFAST Motor Starters iv GWA 4NEB 950 0562 12 ...

Страница 8: ... 4 Assembling and wiring power connectors 3 11 Table 4 1 Process data and process image AS Interface 4 2 Table 4 2 Software requirements for commissioning 4 4 Table 4 3 Requirements for commissioning 4 4 Table 4 4 Testing the wiring from the motor starter to the motor 4 4 Table 4 5 Diagnostics through LED indicators 4 6 Table 4 6 Possible faults and fault handling 4 7 Table C 1 Order numbers for M...

Страница 9: ...ECOFAST Motor Starters vi GWA 4NEB 950 0562 12 ...

Страница 10: ...istical data These motor starters are described in the ECOFAST Motor Starter High Feature manual Topics The manual consists of chapters providing instructions for use and that can be used for reference The following topics are covered Motor starters overview Installation of motor starters Commissioning and diagnostics Wiring and interfaces Device functions Technical data Dimension drawings Order n...

Страница 11: ...ggestions for improvements additional information or correc tions and send the page back to us In this way you will help us improve the next edition of this manual Manuals Two manuals are available ECOFAST Motor Starters this manual ECOFAST Motor Starters High Feature Other system manuals For more information on ECOFAST see the following system manual System ECOFAST ...

Страница 12: ...ch English Motor Starters Overview 1 Section Subject Page 1 1 What are ECOFAST Motor Starters 1 2 1 2 Connections fieldbus interfaces LED indicators 1 2 1 2 1 Connections 1 2 1 2 2 Fieldbus interfaces 1 3 1 2 3 LED indicators 1 3 1 3 Product overview 1 4 ...

Страница 13: ...tching and protecting three phase loads rated at 400 V AC up to 4 kW mechanical switching and up to 5 5 kW soft starter optionally equipped with a 400 V AC brake contact available with a PROFIBUS DP or AS Interface AS i connection 1 2 Connections fieldbus interfaces LED indicators 1 2 1 Connections ECOFAST Motor Starters have the following connections Fig 1 1 Connections on the motor starter AUX P...

Страница 14: ... indicators PROFIBUS DP PROFIBUS DP interface with data terminal and data tee connector optionally for copper cable or fiber optic cable AS i interface using insulation displacement technology for yellow AS i cable data and 24 V non switched and black AS i cable AUX PWR 24 V DC switched AS Interface AS i AS i AUX PWR AS Interface Description SF General fault AS i Fieldbus status AUX PWR 24 V DC sw...

Страница 15: ...1AA0 3RK1 303 5CS41 1AA3 3RK1 303 6BS71 1AA0 3RK1 303 6BS71 1AA3 3RK1 303 6DS71 1AA0 3RK1 303 6DS71 1AA3 Shaded boxes device function for this order number available Light gray fields Description in manual ECOFAST Motor Starters High Feature Order no 3RK1 702 3AB18 1AA0 German Order no 3RK1 702 3BB18 1AA0 English Gray fields Description in this manual ECOFAST Motor Starters Order no 3RK1 702 2GB18...

Страница 16: ...number available Light gray fields Description in manual ECOFAST Motor Starters High Feature Order no 3RK1 702 3AB18 1AA0 German Order no 3RK1 702 3BB18 1AA0 English Gray fields Description in this manual ECOFAST Motor Starters Order no 3RK1 702 2GB18 0AA0 German English Order number Device function Self test Local device interface Electronic switching technology Mechanical switching technolog Eme...

Страница 17: ...Motor Starters Overview ECOFAST Motor Starters 1 6 GWA 4NEB 950 0562 12 ...

Страница 18: ...the vicinity of the motor motor nearby with connecting cable or plug it into the motor directly motor plugged in with mounting plate Section Subject Page 2 1 Setting the address 2 2 2 2 Setup with motor plugged in 2 3 2 2 1 Required components 2 3 2 2 2 Installation 2 4 2 3 Setup with motor nearby 2 5 2 3 1 Required components 2 5 2 3 2 Installation 2 6 ...

Страница 19: ...configu ration hex ID Code hex ID1 Code hex ID2 Code hex of product status1 smaller 10 from 10 3RK1 323 2AS51 1AA0 7 D F F 0 3RK1 323 2AS51 1AA3 7 D F F 0 1 The product status is printed below the addressing socket Step Procedure 1 If you intend to address the motor starter via the addressing socket switch off the AS i supply voltage This is necessary for reasons of system safety 2 Unscrew the scr...

Страница 20: ...ower cable for looping through power Han Q8 pin power tee connector prefabricated or prepared by customer 3RK1 911 0 depending on length and cross section Power cable no looping through of power Han Q8 at both ends prefabricated or prepared by customer 3RK1 911 0 depending on length and cross section 4 AS i cable trapezoidal section yellow rubber 2 x 1 5 mm2 for fieldbus 3RX9 01 0AA00 depending on...

Страница 21: ...e motor starter onto the motor connector Secure the connection with the locking device 3 Connect the AS i cables in accordance with the diagram below Important If the motor starter is the last station on the AS Interface line you must terminate the ends of the AS i cables with cable end covers Order No 3RK1 901 1MN00 in order to obtain degree of protection IP 67 To allow this leave the cable ends ...

Страница 22: ...y customer 3RK1 911 0 depending on length cross section Han 10E one end both ends 4 Power cable for looping through power Han Q8 pin power tee connector prefabricated or prepared by customer 3RK1 911 0 depending on length and cross section Power cable no looping through of power Han Q8 at both ends prefabricated or prepared by customer 3RK1 911 0 depending on length and cross section 5 AS i cable ...

Страница 23: ...rk Take note of the information in the operating instructions Work through the following steps to install the motor starter Step Description 1 Choose a flat surface for installation The distance from the motor depends on the length of the power cable Any required mounting position can be chosen 2 3 Screw the motor starter down onto the flat surface Table 2 6 Installation motor nearby 90 210 Drill ...

Страница 24: ...ree of protection IP 67 To allow this leave the cable ends projecting by about 10 cm beyond the AS i interface 5 Connect the motor starter and motor with the power cable Secure the connections with the locking devices 6 Plug in the power tee connector at the power terminal on the motor starter Secure the connection with the locking device 7 Connect the power cables to the power tee connector Secur...

Страница 25: ...Installation of Motor Starters ECOFAST Motor Starters 2 8 GWA 4NEB 950 0562 12 ...

Страница 26: ... Power Cables Prefabricated at One End with Han Q8 Pin 3 3 3 1 2 Power Cables Prefabricated at One End with Han 10E Pin 3 4 3 2 Wiring rules 3 5 3 2 1 Selecting the power leads 3 5 3 2 2 Unused connections 3 6 3 3 Motor terminal 3 7 3 3 1 Pin assignment 3 7 3 3 2 Preparing power cables 3 8 3 4 Power terminal 3 9 3 4 1 Pin assignment 3 9 3 4 2 Preparing power cables 3 10 3 5 Power tee connectors 3 ...

Страница 27: ...e electric shock and burns Disconnect the system and device from the supply before starting work Danger Ensure that the wiring is carried out carefully and correctly Otherwise motor starters may be destroyed There is potentially lethal danger Caution Note that star jumpers are already wired in the motor starter ...

Страница 28: ...e you can strip the cores and for example attach a plug connector or terminal block Fig 3 1 Numbers printed on the power cable cores 3 1 1 Power Cables Prefabricated at One End with Han Q8 Pin Fig 3 2 Power cables prefabricated at one end with Han Q8 pin 1 2 4 5 1 1 2 2 4 4 3 3 3 5 5 Numbers are printed on the cores for identification purposes The core number pin assignments are specified in the f...

Страница 29: ...r cables prefabricated at one end with Han 10E pin Pin Core no 7 core Core no 11 core Assignment 1 1 1 Phase L1 2 2 2 Phase L2 3 3 3 Phase L3 4 4 Brake reference potential 5 5 Brake 6 4 6 Winding terminal W2 7 5 7 Winding terminal U2 8 6 8 Winding terminal V2 9 9 Temperature sensor terminal a 10 10 Temperature sensor terminal b PE yellow green ...

Страница 30: ...able duct for example the maximum cur rent carrying capacity as a function of ambient temperature is as follows Observe the following rules when carrying out wiring Table 3 1 Rules for wiring 30 C 40 C 45 C 50 C 55 C 1 5 mm2 14 A 12 2 A 11 1 A 9 9 A 8 5 A 2 5 mm2 19 A 16 5 A 15 0 A 13 5 A 11 6 A 4 0 mm2 26 A 22 6 A 20 5 A 18 5 A 15 9 A Rules for flexible cables Data Current carrying capacity of th...

Страница 31: ...Starters 3 6 GWA 4NEB 950 0562 12 3 2 2 Unused connections Close off unused connections with screw caps this is the only way of ensu ring degree of protection IP 65 Order number 3 RK1 902 0CJ00 10 screw caps or 3 RK1 902 0CK00 1 screw cap ...

Страница 32: ... between 400 V AC and 24 V DC is only guaranteed on a motor with safe separation of the temperature sensor circuit with respect to the stator winding 3 3 1 Pin assignment Fig 3 4 Pin assignment for motor terminal 10 9 8 7 6 5 4 3 2 1 Pin Assignment 1 Winding terminal U1 2 Winding terminal V1 3 Winding terminal W1 4 Brake reference potential 5 Brake 6 Winding terminal W2 7 Winding terminal U2 8 Win...

Страница 33: ...he insulation between the motor winding and the temperature sensor in the motor must satisfy the requirements for safe separation The 400 V power supply for the motor and the 24 V DC power supply for the brake are taken over common cables and plug connectors to the loads If the cables are pinched there is a risk of voltage transfer That is why loads with degree of protection Extra low voltage must...

Страница 34: ...r in the event of a fault It is therefore not permissible to connect any loads with the extra low voltage degree of protection to the braking circuit Caution The brake must not be fed from the power supply unit of the 24 V DC swit ched supply AUX PWR black AS i cable 3 4 1 Pin assignment Fig 3 5 Pin assignment for power terminal Pin Assignment 1 Neutral N 2 Phase L2 3 4 Brake 24 V DC optional 5 Br...

Страница 35: ...wer cables with HanQ8 Table 3 3 Preparing connecting leads with Han Q8 You need for connecting the main power on the motor starter power tee connector for looping through the main power from the power tee connector A flexible Cu cable 4 x 2 5 mm2 4 mm2 3 conductors PE 6 x 2 5 mm2 4 mm2 3 conductors PE brake Power connector Han Q8 socket 2 5 mm2 3RK1 902 0CA00 4 0 mm2 3RK1 902 0CB00 Power connector...

Страница 36: ...nnectors Step Procedure 1 Guide the cable through the heavy gauge threaded joint the matching enclosed sealing ring in each case and the connector housing 2 Attach the jacks contact pins to the strands 3 Push the jacks contact pins into the socket insert pin insert until they snap into place 4 Pull the cable back and screw the insert in place in the connector housing with the enclosed screws 5 Scr...

Страница 37: ...s to the power bus The power bus is not interrupted when the motor starter is unplugged Pin assignment Fig 3 7 Pin assignment for power tee connector to motor starter Pin Assignment 1 Neutral N 2 Phase L2 3 4 Brake 24 V DC 5 Brake 0 V DC 6 Phase L3 7 8 Phase L1 9 PE Han Q8 socket Han Q8 socket Direction of power flow Han Q8 pin with power connector ...

Страница 38: ...r 2 and 3 wire circuits Fig 3 8 Pin assignment with circuit examples Note The digital inputs are short circuit proof The current is limited to a maximum of 200 mA In the event of a short circuit or overloading of the sensor supply the switching element motor and brake output are deactiva ted and a general fault is issued You must acknowledge this fault with trip reset Important Do not use an exter...

Страница 39: ...for supplying actuators PELV must be grounded Schematic arrangement The diagram below shows the position and coding of the AS i cables on the motor starter Fig 3 9 AS i interface Contacting The AS i cables are contacted automatically using the insulation piercing method when the AS i cover is screwed on Fig 3 10 Contacting the AS i cables AS i AUX PWR AS i cable Communication and non switched auxi...

Страница 40: ...the supply is restored the disconnection command and the associated signal bits and error bits are acknowledged automatically 24 V DC voltage supply AUX PWR switched black AS i cable This voltage is not constantly available It is only required for driving the switching elements e g a contactor The voltage can be disconnected in the event of an emergency stop or safety shutdown category 1 according...

Страница 41: ...e addressing socket is used for addressing with a device such as the addressing and diagnostic unit This is connected to the addressing socket with the connecting lead Fig 3 11 Addressing socket Addressing socket Connecting lead Screw cap SF AS i AUX PWR STATE IN 1 2 IN 2 ADDR DEVICE X1 X3 Addressing socket ...

Страница 42: ...mmissioning and diagnostics 4 Section Subject Page 4 1 Process data and process images 4 2 4 2 Commissioning and starting 4 4 4 3 Diagnostics through LED indicators 4 6 4 4 Diagnostics with the addressing and diagnostic unit 4 7 4 5 Behavior in the event of faults 4 7 ...

Страница 43: ... Table 4 1 Process data and process image AS Interface Process data Process image 4 outputs DO 0 0 to DO 0 3 4 inputs DI 0 0 to DI 0 3 4 parameters PO 0 0 to PO 0 3 Signal 1 HIGH 0 LOW Outputs Control commands PLC to motor starter DO 0 0 Motor CW 1 ON 0 OFF 1 Motor CCW 1 ON 0 OFF 2 Brake 1 ON 0 OFF 3 Trip Reset 0 1 ACTIVE 0 1 NOT ACTIVE Inputs Signals motor starter to PLC DI 0 0 Ready automatic 1 ...

Страница 44: ...n the event of overload temperature sensor para meter to Warn the motor starter automatically sets the Auto reset para meter to YES As a result the General warning signal is automatically cleared after the cause of the fault is eliminated Self test function with trip reset Note If trip reset output DO 0 3 is applied for longer than 2 seconds and there is no general fault general warning present th...

Страница 45: ...her information is provided in the operating instructions for the addressing and diagnostic unit Configuration software used Explanations Configuration software for the AS i master used See AS i master manual Action assumed to have been taken Further information see 1 Motor starter installed Installation chapter 2 Address set on the motor starter Installation chapter 3 Supply voltage for the motor...

Страница 46: ...upply voltage for motor starter Motor starter sets outputs to 0 and accepts the set address Motor starter receives configurati on data from AS i master Does the configuration data match the actual setup Inputs and outputs enabled data exchange is possible Remedy match configuration data to setup or vice versa AS i and AUX PWR LEDs light up No Yes Ready for operation ...

Страница 47: ...flashing Zero address green Communication and unswitched supply ok off No unswitched supply voltage green Unswitched supply voltage ok off Unswitched supply voltage not ok AUX PWR green Switched supply voltage ok off Switched supply voltage not ok STATE green Circuit state switching element ON by control HMI off Switching element OFF red Circuit state switching command IN 1 green Digital input 1 2...

Страница 48: ...with as follows Table 4 6 Possible faults and fault handling Possible fault Action Indication LEDs Comment Reset Bus fault Tripping AS i Auto Process image fault Tripping SF OFF Undervoltage AS i Tripping SF U 18 V Auto Undervoltage AUX PWR Tripping SF U 18 V Auto Sensor supply overload Tripping SF I 200 mA Trip reset Temperature sensor overload Warning tripping SF Auto Auto reset Trip reset Tempe...

Страница 49: ...dge in the following ways With Trip reset output DO 0 3 Trip reset via fieldbus With a counter command e g Motor off only in the case of a process image fault Automatic acknowledgement depending on parameter PO 0 3 Auto reset only in the case of temperature sensor faults Note If trip reset is applied constantly the acknowledgement is triggered once by edge triggering If trip reset output DO 0 3 is...

Страница 50: ...A 4NEB 950 0562 12 5 1 Deutsch English Device functions 5 Section Subject Page 5 1 Temperature sensor 5 2 5 2 Reversing starter control function 5 3 5 3 Mechanical braking 5 4 6 14 Electronic mechanical switching technology 5 5 ...

Страница 51: ...0660 Parts 302 and 303 Temperature sensor parameter This parameter enables you to determine which temperature sensor is to be used Setting range with parameter PO 0 1 Thermoclick 1 PTC type A 0 Behavior in the event of overload temperature sensor parameter This parameter enables you to determine how you want the motor starter to respond in the event of overloading of the temperature sensor Setting...

Страница 52: ...rmissible to switch from one direction of rota tion to the other after a certain delay During this delay the flywheel of the drive is supposed to come to a standstill The length of the delay depends on which drive is being used and must be taken into account accordingly in the application program Control outputs The direction of rotation is controlled with two outputs DO 0 0 and DO 0 1 Motor CW DO...

Страница 53: ...l circuit for mechanical braking Fig 5 1 Typical circuit for mechanical braking Control output The brake is controlled with output DO 0 2 Brake DO 0 2 1 ON 0 OFF M 3 L1 L2 L3 AC Brake output 10 9 8 7 6 5 4 3 2 1 Pin Assignment 1 Winding terminal U1 2 Winding terminal V1 3 Winding terminal W1 4 Brake reference potential 5 Brake 6 Winding terminal W2 7 Winding terminal U2 8 Winding terminal V2 9 Tem...

Страница 54: ... Only applicable to soft starters Mechanical switching technology The motor starter controls the motor in a 3 phase system with contactors Possible causes of faults The Switching technology device function returns the General fault signal in response to the following causes Switching element defective e g contactor contact welded power semicon ductor failed Switching element overload e g semicondu...

Страница 55: ...Device functions ECOFAST Motor Starters 5 6 GWA 4NEB 950 0562 12 ...

Страница 56: ...B 950 0562 12 A 1 Deutsch English Technical data A Section Subject Page A 1 General technical data A 2 A 2 Auxiliary power A 3 A 3 Digital inputs A 3 A 4 Main power A 4 A 4 1 Mechanical switching A 5 A 4 2 Brake output 400 V AC A 6 ...

Страница 57: ...onal cooling required Housing size H x W x D 90 mm x 130 mm x 250 mm Weight 1 5 kg Operating temperature 20 C to 40 C Storage transport temperature 40 C to 80 C Site altitude 2000 m 4000 m Without restrictions With restrictions e g max ambient temperature lower overvoltage category Vibration strain 3 g ESD 8 kV air discharge 6 kV contact discharge IEC 1000 4 2 severity 3 Electromagnetic fields 10 ...

Страница 58: ...ment contactor on Typically 15 mA switching ele ment contactor off Polarity reversal protection Yes device will not function however Short circuit protection overload protection Yes 0 5A multifuse self healing fuse Reset by power OFF No Undervoltage detection USP 17V DC 17V DC Bridging of power failure 20 ms device is not affected Insulation voltage 500 V DC between the auxiliary voltages and PE I...

Страница 59: ...andard 6 to 20 s 9 to 30 s Rated insulation voltage 500 V AC as per IEC 60947 1 Rated impulse withstand voltage 6 kV as per IEC 60947 1 Safety separation 300 V AC between auxiliary and main power Frequency 50 60 Hz ON duration 100 Short circuit protection Fusible link am 16 A 500VAC Ik 120kA Utilization category 1 Device destroyed after short circuit ...

Страница 60: ... 20 Class 30 Switching capacity AC 3 9 0 A AC 4 6 5 A Control function Direct on line starter reversing starter Switching 3 phase with SIMICONT contactor Switching frequency 50 h with ON duration 50 and ta 1s Waiting time The time between the switch off command and the next switch on command t t tp a e 36 s ton 36 s 1s 35 s I 1 x Ie 1 I 7 2 x Ie 2 50 switching operations h and ON duration 50 Motor...

Страница 61: ...al data ECOFAST Motor Starters A 6 GWA 4NEB 950 0562 12 A 4 2 Brake output 400 V AC Voltage range 100 V AC to 460 V AC Current carrying capacity AC 15 500 mA Short circuit protection Fusible link am 1 A 500VAC ...

Страница 62: ...ECOFAST Motor Starters GWA 4NEB 950 0562 12 B 1 Deutsch English Dimension drawings B Section Subject Page B 1 Motor Sarter B 2 ...

Страница 63: ...ECOFAST Motor Starters B 2 GWA 4NEB 950 0562 12 B 1 Motor Starter Fig 2 1 Motor starter dimension drawing ...

Страница 64: ...arters Reversing starters C 2 C 2 Motor Connection Cables and Power Cables C 3 C 3 Power Control Modules Infeed Modules C 5 C 4 Hybrid Fieldbus Cables C 6 C 5 AS Interface Shaped Cable C 7 C 6 Hybrid Fieldbus Interfaces C 7 C 7 Connectors C 8 C 8 Project engineering software and Documentation C 9 C 9 Tools Connector Sets Configuration C 10 ...

Страница 65: ...OFIBUS DP 3RK1 303 5BS41 1AA3 2 4 A 9 A 4 kW 400 V AC PROFIBUS DP 3RK1 303 5CS41 1AA3 0 3 A 3 A 1 1 kW Thermal Motor Model Mechanical AS Interface 3RK1 323 5BS41 1AA0 2 4 A 9 A 4 kW AS Interface 3RK1 323 5CS41 1AA0 0 3 A 3 A 1 1 kW 400 V AC AS Interface 3RK1 323 5BS41 1AA3 2 4 A 9 A 4 kW 400 V AC AS Interface 3RK1 323 5CS41 1AA3 0 3 A 3 A 1 1 kW Full Motor Protection Electronic Soft PROFIBUS DP 3R...

Страница 66: ...otor starter with the motor for mounting in the vicinity of the motor 7 x 1 5 mm2 1 5 m 7 x 1 5 mm2 3 m any length 7 x 1 5 mm2 3 0 m 7 x 1 5 mm2 3 m to 5 m any length 7 x 1 5 mm2 5 0 m 3RK1 911 0BH10 3RK1 911 0CH20 3RK1 911 0BH20 3RK1 911 0CH30 3RK1 911 0BH30 Han 10 E on both sides to connect the motor starter with the motor for mounting in the vicinity of the motor 11 x 1 5 mm2 1 5 m 11 x 1 5 mm2...

Страница 67: ...2 5 mm2 1 5 m 7 x 2 5 mm2 3 m any length 7 x 2 5 mm2 3 0 m 7 x 2 5 mm2 3 m to 5 m any length 7 x 2 5 mm2 5 0 m 7 x 2 5 mm2 5 m to 10 m any length 7 x 2 5 mm2 10 0 m 7 x 2 5 mm2 10 m to 15 m any length 3RK1 911 0BF10 3RK1 911 0CF20 3RK1 911 0BF20 3RK1 911 0CF30 3RK1 911 0BF30 3RK1 911 0CF40 3RK1 911 0BF40 3RK1 911 0CF50 Han Q8 pin open end 5 x 4 0 mm2 1 5 m 5 x 4 0 mm2 3 m any length 5 x 4 0 mm2 3 ...

Страница 68: ...pply 3 AC 400 V 40 A Auxiliary power supply 2 x DC 24 V 1x AS i Rotary actuator with main switch functions SIGUARD contactor safety combination Autostart Dimensions W x H x D in mm 400 x 650 x 248C 4FB2 121 2AE01 0AA0 PROFIBUS S7 300 master and AS i bus master Main power supply 3 AC 400 V 25 A Auxiliary power supply 2x DC 24 V 1 x AS i Rotary actuator with EMERGENCY STOP functions AS i monitor for...

Страница 69: ...11 0BM20 5 m 3RK1 911 0BM30 10 m 3RK1 911 0BM40 15 m 3RK1 911 0BM50 Unassembled cable 20 m 3RK1 911 0AT60 50 m 3RK1 911 0AT70 100 m 3RK1 911 0AT80 PROFIBUS ECOFAST Hybrid Cable copper Trailing cable PUR casing with two shielded copper conductors for PROFIBUS DP and four copper cores with 1 5 mm2 Pre assembled with two ECOFAST connectors 1 5 m 3RK1 911 0BL10 3 m 3RK1 911 0BL20 5 m 3RK1 911 0BL30 10...

Страница 70: ...0 Table C 5 AS Interface Shaped Cable Description Order No Hybrid fieldbus interface Interface between switchgear cabinet Infeed module IP 20 and the field IP 67 Data via 2 x Copper shielded FO 2 x 24 V DC for switched non switched Voltage Infeeding of Data and 2 x 24 V into the hybrid fieldbus cable 2 channels Hybrid Fieldbus Interface Copper Copper Socket Socket for incoming supply Hybrid Fieldb...

Страница 71: ...copper cable plug connector with 2x shielded copper and 4x copper conductors 1 5 mm2 Contact type POF Han D for data and 24 V with pin insert with socket insert 3RK1 911 2AB00 3RK1 911 2AA00 Power Power Tee Connector Han Q8 individual mounting Power Tee Connector Han Q8 lined up Connector Set Han 10E Pin in thin coupling enclosure PG 16 Connector Set Han 10E Pin in thick coupling enclosure PG 21 C...

Страница 72: ...ystem requirements PROFIBUS DP interface CP5411 ISA CP5412 ISA CP5511 PCMCIA P5611 PCI Smart Cable for serial communication via a serial interface and Teleservice CP5613 and CP5614 new CP card and MPI interface on PG7xx and its driver software view interactive catalog CA01 CD ROM drive STEP7 object manager for integrating the ECOFAST starter as an S7 slave in SIMATIC S7 for calling Switch ES from ...

Страница 73: ... set for power infeed 2 5 mm2 1 connector enclosure with PG 16 1 socket insert and 9 contact socket 4 0 mm2 1 3RK1 902 0CB00 Connector set for looping through power 2 5 mm2 1 connector enclosure with PG 16 1 pin insert and 9 contact pins 2 5 mm2 1 3RK1 902 0CC00 Connector set for looping through power 4 0 mm2 1 connector enclosure with PG 16 1 pin insert and 9 contact pins 4 0 mm2 1 3RK1 902 0CD00...

Страница 74: ... interfaces 1 3 G General technical data A 2 H Han Q8 power connectors 4 9 L LED indicators 1 3 M Main power A 4 Mechanical braking 5 4 Mechanical switching A 5 Mechanical switching technology 5 5 Motor starter dimension drawing B 2 Motor terminal 4 5 P Power cables with Han 10E 4 6 Power cables with HanQ8 4 8 Power tee connectors 4 10 Power terminal 4 7 Preparing power cables 4 6 4 8 Process data...

Страница 75: ...ECOFAST Motor Starter Index 2 GWA 4NEB 950 0562 12 ...

Страница 76: ...ch 1954 92220 Amberg Fax 09621 80 3337 ECOFAST Motor Starters system manual Have you found any typographical errors while reading this manual Please use this form to tell us about them We would also welcome any ideas and suggestions you may have Sender please fill out Name Company Department Address Telephone ...

Страница 77: ...Correction page ECOFAST Motor Starters GWA 4NEB 950 0562 12 ...

Отзывы: