Building Technologies
048_DMS_DF8000_ICC_MP4.15_A6V10081388_c_en.doc
Fire Safety & Security Products
06.2008
4.4
RS485 bus connection
The CPU module is connected on the 2-wire, RS485 bus as shown in Fig. 9. The
RS485 signals have to be connected to terminals 10 and 11.
Fig. 10 RS485 connection
The RS485 bus cable should be TP AGW20 or equivalent. A 100 Ohm resistor
should be installed at both ends of the line (see Fig. 11).
Fig. 11 Termination resistors