![Siemens DF8000 Скачать руководство пользователя страница 35](http://html.mh-extra.com/html/siemens/df8000/df8000_installation-function-and-configuration-commissioning-safety-regulations_381910035.webp)
31
Building Technologies
048_DMS_DF8000_ICC_MP4.15_A6V10081388_c_en.doc
Fire Safety & Security Products
06.2008
8.1.3
NK822x (RS485) connection to DF8003
The cable that links the NK822x to the (first) DF8003 CPU module must be as
shown in Fig. 27.
AWG 22 (0.6 mm
2
) unshielded cable is recommended. Max length is 1200 m.
Fig. 27 RS485 Connection cable from NK822x to DF8003
Max distance from NK822x to
last
DF8003 = 1200 m
10
11
12
13
14
15
16
17
18
9
8
7
6
5
4
3
2
1
1
DF8003
CPU
1
8
FLT
TX
RX
PWR
RST
to next DF8003 unit
-
+
2 1