Application and functions
1.8 Configuration limits and performance data
CP 154xSP-1
24
Operating Instructions, 12/2019, C79000-G8976-C426-05
●
SNMP
As SNMP agent, the CP supports queries via SNMPv1.
The CP 1543SP-1 also supports SNMPv3.
For more detailed information, refer to section SNMP (Page 61).
●
E-mail
The CP 1542SP-1 IRC and CP 1543SP-1 support sending e-mails.
1.8
Configuration limits and performance data
Number of CPs per station
In each ET 200SP station, up to three special modules can be plugged in and configured;
this allows a maximum of two CP 154xSP-1 modules.
For details of the permitted special modules and the slot rules, refer to section Installing the
Connection resources
Connection resources - valid for all CP variants
Number of connections via Industrial Ethernet, maximum of 32 in total, of which:
●
S7: Max. 16
●
TCP/IP: Max. 32
●
ISO-on-TCP: Max. 32
●
UDP: Max. 32
Also:
●
Online connections of the engineering station (STEP 7): Max. 2
●
TCP connections for HTTP
For HTTP access upp to 12 TCP connection resources are available that are used by one
or more Web browsers to display data of the CP.
●
PG/OP connections (HMI): In total maximum of 16,
of which:
–
Connection resources for PG connections: Max. 16
–
Connection resources for OP connections: Max. 16
Содержание CP 1542SP-1
Страница 8: ...Preface CP 154xSP 1 8 Operating Instructions 12 2019 C79000 G8976 C426 05 ...
Страница 12: ...Table of contents CP 154xSP 1 12 Operating Instructions 12 2019 C79000 G8976 C426 05 ...
Страница 86: ...Program blocks 5 3 MODBUS blocks CP 154xSP 1 86 Operating Instructions 12 2019 C79000 G8976 C426 05 ...
Страница 106: ...Approvals CP 154xSP 1 106 Operating Instructions 12 2019 C79000 G8976 C426 05 ...
Страница 116: ...Documentation references 10 CP 154xSP 1 116 Operating Instructions 12 2019 C79000 G8976 C426 05 ...