Installation, wiring, commissioning
3.2 Installing the CP
CP 154xSP-1
Operating Instructions, 12/2019, C79000-G8976-C426-05
43
NOTICE
Installation location - Dependency of the temperature range
The module must be installed so that its upper and lower ventilation slits are not covered,
allowing adequate ventilation. Above and below the modules, there must be a clearance of
25 mm to allow air to circulate and prevent overheating.
Note the dependency of the permitted temperature range on the installation location:
•
Horizontal installation of the rack (DIN rail) means vertical position of the CP.
•
Vertical installation of the rack (DIN rail) means horizontal position of the CP.
You will find the permitted temperature ranges in the section Technical specifications
(Page 99).
Installation of the rack
Installation position of the CP
Horizontal installation of the rack
Vertical installation of the rack
Slot rules
The CPU always occupies slot 1. In an ET 200SP you can plug in up to three of the following
modules in slots 2 ... 4 (see figure) to the right of the CPU:
●
CMs
●
CPs
●
BusAdapter Send
Of these three modules, up to two CP 154xSP-1 modules can be plugged in. These two CPs
can be of the same type or different.
The CM DP can only be plugged in directly next to the CPU.
Содержание CP 1542SP-1
Страница 8: ...Preface CP 154xSP 1 8 Operating Instructions 12 2019 C79000 G8976 C426 05 ...
Страница 12: ...Table of contents CP 154xSP 1 12 Operating Instructions 12 2019 C79000 G8976 C426 05 ...
Страница 86: ...Program blocks 5 3 MODBUS blocks CP 154xSP 1 86 Operating Instructions 12 2019 C79000 G8976 C426 05 ...
Страница 106: ...Approvals CP 154xSP 1 106 Operating Instructions 12 2019 C79000 G8976 C426 05 ...
Страница 116: ...Documentation references 10 CP 154xSP 1 116 Operating Instructions 12 2019 C79000 G8976 C426 05 ...