The parameters stored in the burner control LME39… can be displayed and changed
on the parameter level.
VSD
A
F
>1 s
Press button combination
VSD
A
F
to display
000: Int
.
With
, select the parameter group
100:
PArA
.
With
, select the parameter group
100:
PArA
.
Pressing the
/reset
button takes you to
parameter
182:
Flame sensitivity.
20.1
Parameters without index, with direct
display
20.1.1
Example of parameter 226 (preignition time) on the
parameter level
P
V
h min s
%
B
ild
1
8
6/
11
0
7
Press
to select preignition time.
Display: Parameter
226:
flashes, value
3.675
does not.
/reset
or
P
V
h min s
%
B
ild
167
/1
1
0
7
Press
or
to go to editing mode.
Display:
3.675
or
P
V
h
min s
%
B
ild
168
/1
107
Press
or
to shift the former
preignition time to change mode one place to
the left.
Display: Preignition time
3.675
flashes.
Note!
To detect display errors, the value appears
one place shifted to the left.
or
P
V
h
min s
%
B
ild
169
/1
107
Press
or
to select the required
preignition time.
Display: Preignition time
3.822
flashes