Control via the operator panel
4.6 Menu commissioning / service
Cabinet Modules Operator Panel AOP30
54
Operating Instructions, 04/2014, A5E03263551A
Daylight-saving time changeover (factory setting: No)
●
No
The time does not automatically change over to daylight-saving time.
●
Yes
Selection is only possible if synchronization is set to "None" or "AOP -> Drive".
The time is then automatically set to summer or winter time.
After the changeover - for synchronization "AOP -> Drive" - synchronization is
immediately carried out, irrespective of the synchronization interval set.
Changes to the synchronization must be saved with "Save".
Date format
In this menu, the date format can be set:
●
DD.MM.YYYY: European date format
●
MM/DD/YYYY: North American date format
4.6.4.4
DO name, display mode
Using the setting option "User-defined DO name" "No/Yes", you can toggle the display of the
DO name between the standard abbreviation (e.g. A_INF, VECTOR; CU_S) and a DO name
of your own choice (e.g. Infeed_1, Motor_1).
User-defined DO name (factory setting: NO)
●
Yes: The "User-defined DO name" stored in parameter p0199 is displayed instead of the
standard DO abbreviation.
●
No: The standard DO abbreviation is displayed.
4.6.4.5
Normalization to motor current
The reference variable for the bar-type display of parameter r0027 (smoothed absolute
current actual value) can be changed over in the operating screen forms in this menu.
Normalization to motor current (factory setting: NO)
●
Yes:The bar-type display of parameter r0027 in the operating screen form is displayed
referred to parameter p0305 (rated motor current).
●
No:The bar-type display of parameter r0027 in the operating screen form is displayed
referred to parameter p2002 (reference current).