Control via the operator panel
4.8 Operation via the operator panel (LOCAL mode)
Cabinet Modules Operator Panel AOP30
62
Operating Instructions, 04/2014, A5E03263551A
4.8.11
Operator input inhibit / Parameterization inhibit
To prevent users from accidentally actuating the control keys and changing parameters, you
can activate an operator input / parameterization inhibit using a key-operated pushbutton.
Two key icons appear in the top right of the display when these safety inhibits are enabled.
Table 4- 10 Display of operator input / parameterization inhibit
Inhibit type
Online operation
Offline mode
No safety inhibit
Operator input inhibit
Parameterization inhibit
Operator input i parameterization inhibit
Settings
Figure 4-14 Set safety inhibits
The "Operator input inhibit" setting can be changed directly via <F5> "Change" once you
have selected the selection field.
When "Parameterization inhibit" is activated, you have to enter a numeric password (repeat
this entry). You must also enter this password when deactivating "Parameterization inhibit".
Operator input inhibit (factory setting: not active)
●
Active: The parameters can still be viewed, but a parameter value cannot be saved
(message: "Note: operator input inhibit active"). The OFF key (red) is enabled. The
LOCAL/REMOTE, ON (green), JOG, CW/CCW, HIGHER and LOWER keys are disabled.
Parameterization inhibit (factory setting: not active)
●
Active: Parameters cannot be changed unless a password is entered. The
parameterization is the same as in the operator input inhibit state. If you try and change
parameters, the message: "Note: Parameterization inhibit active" is displayed. All the
control keys, however, can still be actuated.