Commissioning
3.4 Initial commissioning
Cabinet Modules Operator Panel AOP30
26
Operating Instructions, 04/2014, A5E03263551A
Note
Selecting the motor type
The selection of the motor type pre-assigns specific motor parameters and optimizes the
operating characteristics and behavior. Details are described in the List Manual in the p0300
parameter.
Note
Selecting a listed motor (p0300
≥
100)
When selecting a mot
or type ≥
100, the order number of the associated motor can be
selected via drop-down list.
Basic commissioning: Entering the encoder data (if available)
When the SMC10/SMC20/SMC30 is connect-
ed for encoder evaluation (with options K46,
K48, and K50), it is recognized by the AOP30
and a screen is displayed in which you can
enter the encoder data.
Navigate within the selection fields with <F2>
and <F3>.
Activate your selection with <F5>.
Predefined encoders can be easily set by selecting parameter p0400 (encoder type
selection):
Encoders for SMC10:
1001:
Resolver 1 speed
1002:
Resolver 2 speed
1003:
Resolver 3 speed
1004:
Resolver 4 speed