7
AOP Operating Instructions – Issue 07/05
6SE6400-5AP00-0BB0
2.2.1 Network
control
– selecting Inverters
From the top-level menu select operate: Attached network of drives are then
checked and for each connected drive an ‘
O
’ should appear.
If there is a fault on a connected drive ’
F
’ should appear- use
and
to
select the drive and clear the fault.
2.2.2 Network
control – Broadcast Mode
From the top-level menu select operate: Attached network of drives are then
checked and for each connected drive an ‘
O
’ should appear.
Select ‘B’ and press
to enter Broadcast mode of operation, at any time
will leave this mode.
2.2.3
Network control – PC Mode
The AOP may be configured as an RS232 to RS485 converter. This will allow a
PC running software such as DriveMonitor to connect to a network of drives, as
described above.
To enter this mode select PC from the Mode menu followed by the desired baud
rate of operation. The PC should be connected to the PMK using a Null Modem
lead, as described in the PMK brochure.
2.3 Parameter
Upread
Important Notes
¾
Support of drive inverters MICROMASTER 440.
The AOP will normally only upload and download parameters up to
and including level 3. When copying parameter sets between
inverters the user must again
complete
the quick commissioning and
the motor identification for the inverter to modify internal parameters
(level 4). This is important for sensor less vector control. To do this
set P1910 = 3.
Alternatively the commissioning PC software "STARTER" may be
used to perform upread/download completely in order to clone a
MICROMASTER 440.
¾
Memory Limitation
The delivered AOP supports five European Languages of English,
German, French, Spanish and Italian.
Due to internal memory
limitations the user should delete one of these languages in
order to upread the specified ten parameter sets that can be held
on the AOP.
¾
To Delete a Language
To do this Select “Language” from the top level menu, highlight the
language you want to delete then press “Fn” and “
↑
”.
Please note
that once a Language has been removed it cannot be restored.
The upread facility allows a user to read the parameter set from an inverter to
the AOP and store the parameter set within the AOP’s internal memory. The
AOP can read from a single inverter in local mode or from one specified inverter
on a network of inverters in master mode.
The AOP can upread up to 10 parameter sets from the connected inverters, the
number of sets will depend on the type of inverters that are connected to the
AOP. For more details on available memory see P8562 in the relevant
parameter list or Section 2.5 on page 10 of this manual. It should be noted that
the timer settings also use AOP memory.