3/8
Siemens
Electrical Actuators
CA1Q4895en
Building Technologies
2016-03-24
Plastic cover
Position indication
Locking-proof, maintenance-free gear train
Manual adjustment with rotary knob
Reduced power consumption in the holding positions
Load-dependent switch-off in the event of overload and in stroke end positions
Notes
The actuators must be electrically connected in accordance with local regulations (refer
to «Connection diagrams»).
Regulations and requirements to ensure the safety of people and property must
be observed at all times!
The permissible temperatures must be observed (refer to «Technical data»).
Mounting Instructions 4 319 5614 0 are enclosed with each pack.
Assembly is made with the coupling nut; no tools or adjustments are required. The
actuators should be installed so that they are initially in position 0 (also refer to «Manual
override»).
90°
43
6
2Z
01
90°
When commissioning the system, check wiring and the functions of the actuator.
Before testing the functioning of the SSC.., always check to ensure that the
actuator concerned is mounted on a valve (refer to «Equipment combinations»).
Calibrating the SSC619 without a valve connected causes the actuator to lock in
position 1. To recalibrate (after mounting on a valve), disconnect power and reset the
stroke manually from position 1 to 0 (refer to «Recalibration»).
The rotary knob can be used to drive the actuator into any position between 0 and 1. If a
control signal from the controller is present, this will take priority in determining the
position.
To retain the manually set position, unplug the connecting cable or switch off the rated
voltage and the control signal.
Features and benefits
Engineering
Caution
Mounting
Orientation
Commissioning
Caution
Operation
Note