background image

5/8

Siemens

Electrical Actuators

CA1Q4895en

Building Technologies

2016-03-24

Technical data

SSC319

SSC819

SSC619

Power supply

Rated voltage

Voltage tolerance

AC 230 V

± 15 %

AC 24 V

± 20 %

AC 24 V or DC 24 V

± 20 %

Rated frequency

50 / 60 Hz

Max. power consumption

6 VA

0.8 VA

2 VA

Fuse for incoming cable

2 A, quick blow

Control

Control signal

3-position

DC 0...10 V

Input impedance for DC 0...10 V

> 100 kOhm

Positioning accuracy for DC 0...10 V

< 2 % of nominal

stroke

Parallel operation
(number of actuators)

1)

max. 10

Functional data

Running time 5.5 mm stroke at 50 Hz

150 s

30 s

Nominal stroke

5.5 mm

Nominal force

300 N

Permissible temperature of

medium in the connected valve

1...110 °C

Electrical connections

Terminal block

, pluggable

screw terminals for max. 3 mm

2

Terminal block color

green

grey

red

Cable strain relief

for cables 4...11 mm dia.

 Norms and directives

Electromagnetic compatibility
(Application)

For residential, commercial and light- industrial

environments

Product standard

EN60730-x

EU Conformity (CE)

A5W90000898

A5W90000900

A5W90000899

RCM Conformity

A5W90000923_A A5W90000925_A

A5W90000924_A

EAC Conformity

Eurasia Conformity

Protection class to EN 60730

II

III

Contamination level

EN 60730, Class 2

Housing protection

Upright to horizontal

IP40 to EN 60529

UL approbation

UL 873

cUL approbation

C22.2 No. 24-93

Environmental compatibility

The product environmental declaration CE1N4895en01

contains data on environmentally compatible product

design and assessments (RoHS compliance, materials

composition, packaging, environmental benefit,

disposal).

Dimensions / weight

Dimensions

refer to «Dimensions»

Coupling thread to valve

coupling nut G¾ inch

Weight

0.26 kg

0.25 kg

Housing colors

Base, rotary knob
Cover

RAL 7035, light-grey

1)

  Provided the controllers’ output is sufficient

General

ambient conditions

Operation

EN 60721-3-3

Transport

EN 60721-3-2

Storage

EN 60721-3-1

Environmental conditions

class 3K3

class 2K3

class 1K3

Temperature

+5...+50 °C

–25...+70 °C

–25...+70 °C

Humidity

5...95 % r.h.

< 95 % r.h.

5...95 % r.h.

Содержание acvatix SSC319

Страница 1: ...AC DC 24 V DC 0 10 V control signal Nominal force 300 N Automatic identification of valve stroke Direct mounting with coupling nut no tools required Cable connection via screw terminals Manual override with indication of position and direction of travel Parallel connection of multiple actuators Use For operation of Siemens 2 port and 3 port valves with a nominal stroke of 5 5 mm for water side con...

Страница 2: ...ds valve opens Voltage at Y2 Actuator stem retracts valve closes No voltage at Y1 or Y2 Actuator maintains the current position The valve opens closes in proportion to the control signal at Y At DC 0 V the valve is fully closed A AB When power supply is removed the actuator maintains its current position When the AC DC 24 V supply is applied for the first time the actuators calibrate themselves in...

Страница 3: ...rs should be installed so that they are initially in position 0 also refer to Manual override 90 4362Z01 90 When commissioning the system check wiring and the functions of the actuator Before testing the functioning of the SSC always check to ensure that the actuator concerned is mounted on a valve refer to Equipment combinations Calibrating the SSC619 without a valve connected causes the actuator...

Страница 4: ...place The SSC actuators cannot be repaired They must be replaced as a complete unit Disposal The device is considered an electronics device for disposal in terms of European Directive 2012 19 EU and may not be disposed of as domestic garbage Dispose of the device through channels provided for this purpose Comply with all local and currently applicable laws and regulations Warranty The technical re...

Страница 5: ...r residential commercial and light industrial environments Product standard EN60730 x EU Conformity CE A5W90000898 A5W90000900 A5W90000899 RCM Conformity A5W90000923_A A5W90000925_A A5W90000924_A EAC Conformity Eurasia Conformity Protection class to EN 60730 II III Contamination level EN 60730 Class 2 Housing protection Upright to horizontal IP40 to EN 60529 UL approbation UL 873 cUL approbation C...

Страница 6: ...24 V Connection diagrams 4864A01 L N L N AC 230 V N Y2 Y1 2AF N Y1 Y2 Q1 Q2 Y N Controller Y Actuator L System potential AC 230 V N System neutral Y1 Y2 Control signal OPEN CLOSE Q1 Q2 Controller contacts 4864A02 Y1 G G0 SP SN AC 24 V G Y2 Y1 Y2 N Q1 Q2 2AF Y N Controller Y Actuator SP G System potential AC 24 V SN G0 System neutral Y1 Y2 Control signal OPEN CLOSE Q1 Q2 Controller contacts 4864A03...

Страница 7: ...ors CA1Q4895en Building Technologies 2016 03 24 Dimensions All dimensions in mm 48 110 8 89 2 21 6 115 1 132 5 4895Z08 G Revision numbers Type reference Valid from Rev No Type reference Valid from Rev No SSC319 J SSC619 J SSC819 J ...

Страница 8: ...d by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2007 Technical specifications and availability subject to change without notice ...

Отзывы: