50 / 92
Siemens
Actuators SAX.., SAY.., SAV.., SAL.. for valves
CE1P4040en
Building Technologies
Handling
2018-12-05
Action
Pushbutton operation
Feedback message
Current Modbus address
(starting from lowest address
position)
Button pressure < 1s
1st digit: red
2nd digit: green
3rd digit: orange
The LED blinks blue once after address
indication and when bus termination is On
Example:
124 = 4x red, 2x green, 1x orange
Switches bus termination On/Off
Switch-on 1. Press button 3x
Blinking or flickering of LED stops
(termination mode)
2. Press button 1x briefly
Blue LED blinks once
3. Press button until the LED
turns red
RED LED is lit (confirmation)
4. Release button
LED not lit
Address is indicated
LED blinks blue once following address
indication
Device enters normal mode
Switch-off 1. Press button 3x
Blinking or flickering of LED stops
(termination mode)
2. Press button until the LED
turns red
RED LED is lit (confirmation)
3. Release button
Device enters normal mode
Enter Modbus address using
pushbutton
Press button > 1s and < 5s
See “Enter address using pushbutton”,
page 51
Enable pushbutton addressing
(together with Climatix
TM
controllers)
1. Press button > 5s and < 10s
2. Release button
Red LED is lit and goes off after 5 s
Orange LED is lit
Reset to factory settings
Press button > 10s
Orange LED blinking
Color
Blinking pattern
Description
Green
1s On / 5s Off
Normal mode without bus traffic
Flickering
Normal mode with bus traffic
Orange / green
1s orange / 1s green
Device is in override control mode
Orange
1s On / 1s Off
Bus parameter not yet configured
1s On / 5s Off
Device is in backup mode (replacement mode)
Red
Permanently lit
Mechanical error, device blocked, manual
intervention or calibration
1s On / 5s Off
Internal error
0.1s On / 1s Off
Invalid configuration, e.g. Min = Max
Blue
Flickering once after address indication
Bus termination active
User interface
Pushbutton operation
LED colors and
blinking patterns