22 / 92
Siemens
Actuators SAX.., SAY.., SAV.., SAL.. for valves
CE1P4040en
Building Technologies
Engineering
2018-12-05
2.8
Spare parts
The following spare part sets are available:
Stock number
8000060843
Housing cover
Screw
(valve stem coupling)
U
-
bracket
Single components from the spare part sets are not available.
Stock number
8000060844
Housing cover
2 adapters
1 pc. 14 mm
1 pc. 11 mm
4 screws
2 pcs. M5 x 20 mm
2 pcs. M6 x 20 mm
Single components from the spare part sets are not available.
2.9
Sizing
2.9.1
Parallel operation of actuators
3
-
position actuators must have one specific controller each, refer to "Connection
Up to 10 actuators can drive in parallel on a controller output with a rating of 1 mA.
Modulating actuators have an input impedance of 100 kΩ.
The Modbus converter is designed for analog control on 0..10 V on the actuator
side.
Note
: Keep the setting of the analog signal on the actuator as is (switch 1 to
"OFF"), adjustment is not allowed.
The actuators are factory
-
set to equal
-
percentage characteristic curve.
Note
: The DIL switch (actuator
-
internal changeover of characteristic curve) must be
set to "log" (switch 2 to "OFF").
SAY.., SAX.., SAV..
SAL..
SA..31.. and SA..81..
SA..61..
SAX61../MO