English
56
C53000-B1174-C151-1
– Energy-rich surge voltages
IEC 61000–4–5; Installation Class
III
(SURGE)
– Line conducted HF, amplitude module.
IEC 61000–4-6, Class
III
– Magnetic field with electrical frequency
IEC 61000–4–8, Class
IV,
IEC 60255–6
frequency
– Fast Transient Surge Withstand Capability
ANSI/IEEE C37.90.1
– Fast Transient Surge Withstand Capability
ANSI/IEEE C37.90.1
– Radiated Electromagnetic Interference
ANSI/IEEE Std C37.90.2
– Dampened oscillations
IEC 60694, IEC 61000–4–12
EMC tests for emitted interference
EN 50081–1 (generic standard)
(Type test)
– Radio noise voltage to lines
IEC–CISPR 22 limit value B
– Radio noise field stength
IEC–CISPR 22 limit value Class B
– Voltage fluctuations
IEC 61000–3–3
Vibration and shock stress IEC 60255–21
and
IEC 60068
Shock stress on stationary deployment
– Vibration IEC 60255–21–1,
Class 1,IEC 60068–2-6
– Shock
IEC 60255–21–2, Class 2, IEC 60068–2–27
– Seismic vibration
IEC 60255–21–2, Class 2, IEC 60068–3–3
Vibration and shock stress IEC 60255–21
and
IEC 60068–2
During transport
– Vibration
IEC 60255–21–1, Class 2, IEC 60068–2–6
– Shock
IEC 60255–21–2, Class 1, IEC 60068–2–27
– Continuous shock
IEC 60255–21–2, Class 1, IEC 60068–2–29
Temperatures IEC
60068–2
– Recommended temperature during operation –5 °C to +55 °C
– Permissible temporary (transient)
operating temperature
–20 °C to +70 °C
– Limit temperatures during storage
–25 °C to +55 °C
– Limit temperatures for operation
–25 °C to +70 °C
Storage and transport of the device with factory packaging!