English
46
C53000-B1174-C151-1
Strip the connecting wires to a length of 6 mm, insert them into the screw terminals as far as
they will go in, and secure them so that they will not slip out while tightening the screw. After
tightening the screws, verify that the wires to the terminals are tightly connected.
Signal connections
Direct connection: Solid or stranded conductors with end ferrules
for cross-sections of 0.13 mm
2
to 0.52 mm
2
, corresponding to AWG 26 to 20.
Use copper conductors only!
Voltage connections
Direct connection: Solid or stranded conductors with end ferrules
for cross-sections of 0.13 mm
2
to 0.52 mm
2
, corresponding to AWG 26 to 20.
Use copper conductors only!
DSUB–connector
A 15-pole DSUB–connector serves as the connection for the interface X.21 (Figure 24).
Standard 15-pin D-subminiature plug connectors conforming to MIL–C–24308 and DIN 41652
can be used.
Figure 24 DSUB–connector
The 15-strand data line should be twisted and, if possible, screened. The pin assignment can
be seen in Figure 25. The byte–timing is not supported. The cable length for the maximum
transmission speed (512 kBit/s) must be
≤
100 m (300 ft). Between the CC–S
0
and the X.21
interface of the communication device, it is recommended to have short connenctions, in
order to avoid electrical interferences. The CC–S
0
should be installed near to the communi-
cation device (DCE).
Содержание 7XV5662-0AB00
Страница 36: ...Deutsch 7XV5662 0AB00 36 C53000 B1174 C151 1 ...
Страница 59: ...7XV5662 0AA00 DD C53000 B1174 C134 4 59 ...