14.01.2002
Active Mini-Starcoupler
Page 37 from 52
This parameter defines a supervision time (1-59 minutes) for the
interface, which expiration leads to an automatic termination of an active
connection between Master – and Slaveport (of the Active Transmission
Mode), if no data is sent or received via the Master-port in this time
period. Also the time set for the selected slave port is supervised.
The timer is set in minutes, seconds and milliseconds (10 ms resolution),
and expires if no data traffic is recognized during that time.
You can confim the actual setting (5 min --> 05:00:00) either with <ESC>
or set it with the entry of 05:00:00 (please note the format 05:00:00). If
another timeout value is set it´s valid for all other Master-ports.
NOTE!
.In individual or master devices, the timeout-time of the master
interfaces must be set greater than the timeout time of the slave
interfaces.The timeout time of the master interfaces in all the slave
devices must be greater than the timeout time of the master interfaces in
the master devices.
To shorten the setting procedure for a time period from 1-59 min only ´
5
´
must be entered here:
Answer On(1000)<return>(1000)<return>(1000)? (Y/N)
<ESC> Keep Current Setting
This dialogue appears only if the port number is selected with 0 (Master
port). It defines, if a <Return> lead to the PROMPT
REMOTE>
in the
terminal program during the normal operation mode or not.
ATTENTION!
For Active Mini-Starcouplers in stand alone operation (only
one unit) or for the unit which is connected nearest to the PC/modem in
a casading operation mode this setting for the Master-port must be ´
Y
´.
It´s a need for the operation together with DIGSI, because a
REMOTE>
indication is necessary, before an active port can be switched from the
program.
Enter ´
Y
´ here to come to the following dialogue:
Generate PING?(Y/N)
<ESC> Keep Current Setting
With the entry of ´
Y
´ an automatic synchronisation of a modem
connected to the Master interface is possible. Every 15 s the string
ATE0Q1
REMOTE>
Содержание 7XV5550-0xA00 Series