![Siemens 7SV512 Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/siemens/7sv512/7sv512_instruction-manual_382645018.webp)
Technical data
7SV512
V1
C53000---G1176---C91
18
3.1.2 Electrical tests
Insulation tests
Standards:
IEC 60255---5
--- High voltage test (routine test)
2 kV (rms); 50 Hz
except d.c. voltage supply input
--- High voltage test (routine test)
2.8 kV dc
only d.c. voltage supply input
--- Impulse voltage test (type test)
5 kV (peak); 1.2/50 s; 0.5 J; 3 positive
all circuits, class
III
and 3 negative shots at intervals of 5 s
EMC tests; immunity
(type tests)
Standards:
IEC 60255---6, IEC 60255---22 (product standards)
EN 50082---2 (generic standard)
VDE 0435 /part 303
--- High frequency
2.5 kV (peak); 1 MHz; =15 s; 400 shots/s;
IEC 60255---22---1, class
III
duration 2 s
--- Electrostatic discharge
4 kV/6 kV contact discharge; 8 kV air discharge;
IEC 60255---22---2 class
III
both polarities; 150 pF; R
i
= 330
and IEC 1000---4---2, class
III
--- Radio-frequency electromagnetic field,
10 V/m; 27 MHz to 500 MHz
non-modulated; IEC 60255---22---3 (report) class
--- Radio-frequency electromagnetic field,
10 V/m; 80 MHz to 1000 MHz; 80 % AM; 1 kHz
amplitude modulated; IEC 1000---4---3, class
--- Radio-frequency electromagnetic field, pulse
10 V/m; 900 MHz; repetition frequency 200 Hz;
modulated; IEC 1000---4---3/ENV 50204, class
duty cycle 50 %
--- Fast transients
IEC 60255---22---4 and IEC 1000---4---4, class
2 kV; 5/50 ns; 5 kHz; burst length 15 ms;
repetition rate 300 ms; both polarities; R
i
= 50 ;
duration 1 min
--- Conducted disturbances induced by
radio-frequency fields, amplitude modulated
10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz
IEC 1000---4---6, class
III
--- Power frequency magnetic field
IEC 1000---4---8, class
IV
30 A/m continuous; 300 A/m for 3 s; 50 Hz
IEC 60255---6
0.5 mT; 50 Hz
EMC tests; emission
(type tests)
Standard:
EN 50081---
K
(generic standard)
--- Conducted interference voltage, aux. voltage
150 kHz to 30 MHz
CISPR 22, EN 55022, class B
--- Interference field strength
30 MHz to 1000 MHz
CISPR 11, EN 55011, class A
www
. ElectricalPartManuals
. com