Operating instructions
7SV512
V1
105
C53000---G1176---C91
6.8
Putting the relay into operation
All setting values should be checked again, in case
they were altered during the tests. Particularly check
that all desired protection and ancillary functions
have been programmed in the configuration param-
eters (address block 78, refer to Section 5.4) and all
desired protection functions have been switched
ON
.
The counters for circuit breaker operation statistics
should be erased (address block 82, refer to Section
6.5.2).
Push the key
M/S
on the front. The display shows
the beginning of the annunciation blocks. Thus, it is
possible that the measured values for the quiescent
state of the relay can be displayed (see below).
These values has been chosen during configuration
(refer to Section 5.3.2) under the addresses 7005
and 7006.
Stored indications on the front plate should be reset
by pressing the push-button ”RESET LED” on the
front so that from then on only real faults are indi-
cated. From that moment the measured values of
the quiescent state are displayed. During pushing
the RESET button, the LEDs on the front will light up
(except the ”Blocked”---LED); thus, a LED test is per-
formed at the same time.
Check that the module is properly inserted. The
green LED must be on on the front; the red LED must
not be on.
Close housing cover.
All terminal screws --- even those not in use --- must
be tightened.
If a test switch is available, then this must be in the
operating position.
The protection relay is now ready for operation.