7SG12 DAD N Relay Settings
©2010 Siemens Protection Devices Limited
Chapter 3 Page 5 of 20
Description Range
Default
Setting
Selects whether the 87/50-1 Element is
enabled.
87/50-1 Setting
Pickup level
0.005,0.006…2.000 xIn 0.500
xIn
87/50-1 Delay
Pickup delay
0,0.005…60 s
0.00 s
87/50-2 Element
Selects whether the 87/50-2 Element is
enabled.
Disabled, Enabled
Disabled
87/50-2 Setting
Pickup level
0.005,0.006…2.000 xIn 0.500
xIn
87/50-2 Delay
Pickup delay
0,0.005…60 s
0.00 s
1.4 CT Supervision Menu
Description Range
Default
Setting
CT 50 Element
Selects whether the CT supervision
element is enabled.
Disabled, Enabled
Disabled
CT 50 Setting
Pickup level
0.001,0.002…2.000 xIn 0.100
xIn
CT 50 Delay
Pickup delay
0.1,0.2…60 s
10.00 s
1.5 Trip Circuit Menu
Description Range
Default
Setting
Trip Cct Fail 1
Selects if this trip circuit logic is enabled
or disabled.
Disabled, Enabled
Disabled
Trip Cct Fail 1 PU Delay
Delay before trip circuit failure picks up.
Use in conjunction with STATUS INPUT
MENU/Trip Cct Fail 1 setting to configure
which status inputs prevent this timer
from operating.
0,0.02…60 s
0.40 s
Trip Cct Fail 2
Disabled, Enabled
Disabled
Trip Cct Fail 2 PU Delay
0,0.02…60 s
0.40 s
1.6 Status Input Menu
Description Range
Default
Setting
87/50-1 Inhibit
Selects which inputs inhibit the 87/50-1
element
NONE, 1…27
1
NONE
87/50-2 Inhibit
Selects which inputs inhibit the 87/50-2
element
NONE, 1…27
1
NONE
CT 50 Inhibit
Selects which inputs inhibit the CT 50
element
NONE, 1…27
1
NONE
Trip Cct Fail 1
Select which inputs block Trip Cct Fail 1
timer.
If any of the selected inputs is energised
then the trip circuit timer 1 is blocked.
NONE, 1…27
1
NONE
Trip Cct Fail 2
Select which inputs block Trip Cct Fail 2
timer.
NONE, 1…27
1
NONE
Trigger Wave Rec
Selects which inputs can trigger a
waveform record
NONE, 1…27
1
NONE
Trigger Data Rec
Selects which inputs can trigger a data
NONE, 1…27
1
NONE
Содержание 7SG12 DAD-N
Страница 2: ......