7SG12 DAD-N Communication Interface
Personal Computer
Data Concentrator /
Control system
Personal Computer
Modem
PSTN : Public Switched Telephone Network
- Both Dialogue type and Automatic comms :
- Automatic type : continuous interrogation of all relays by
cyclical polling.
- Dialogue type comms. can be initialised from MMI also
EMS Remote
Control Points
P
S
T
N
Modem
Modem
Serial optical links
Cyclical
polling
Man-Machine
Interface
Tx
Rx
Tx
Rx
Tx
Rx
Figure 5 – Direct Control System/Data Concentrator Configuration
Fibre Optic Serial Loop Link
Tx
Tx
Tx
Tx
Rx
Rx
Rx
Rx
Remote System
Tx
Rx
Laptop computer
Remote
RS232
Local
RS232
SIGMA 3
RS232
RS232
Figure 6 – Automatic switchover remote to local control using the SIGMA-3
When a portable PC is plugged into the front port of a SIGMA-3 then the remote system is automatically
disconnected to ensure local control only. Alternatively on Modular II relays the portable PC may be plugged
directly into the front fascia RS232 connection.
©2010 Siemens Protection Devices Limited
Chapter 4 Page 9 of 10
Содержание 7SG12 DAD-N
Страница 2: ......