7SG12 DAD N Relay Settings
©2010 Siemens Protection Devices Limited
Chapter 3 Page 4 of 20
1 DAD-N-101 Relay Setting List
1.1 System Config Menu
Description Range
Default
Setting
Active Group
Selects which settings group is currently
activated
1,2…8
1
View/Edit Group
Selects which settings group is currently
being displayed
1,2…8 1
Default Screens Timer
Selects the time delay after which, if no
key presses have been detected, the
relay will begin to poll through any
screens which have been selected as
default instruments screens
OFF, 1,2,5,10,15,30,60 min
60 min
Backlight timer
Controls when the LCD backlight turns
off
OFF, 1,2,5,10,15,30,60 min
5 Min
Date Date
1/1/1980
Time Time
00:00:00
Select Grp Mode
Mode of operation of group change from
status input. Edge triggered ignores the
status input once it has changed to the
relevant group, where as with Level
triggered the relay will only stay in the
group it has changed to whilst the status
input is being driven, after which it
returns to the previous group.
Edge triggered,
Level triggered
Edge triggered
Clock Sync. From Status
Real time clock may be synchronised
using a status input (See Clock Sync. in
Status Input Menu)
Disabled, Seconds,Minutes
Minutes
Operating Mode
To allow access to change configuration
files using Reylogic Toolbox the relay
must be placed Out Of Service.
Local, Remote, Local Or
Remote, Out Of Service
Local Or Remote
Change Password
Allows a 4 character alpha code to be
entered as the password. Note that the
display shows a password dependant
encrypted code on the second line of the
display
AAAA…ZZZZ
“NONE” displayed as
“NOT ACTIVE”
Relay Identifier
An alphanumeric string shown on the
LCD normally used to identify the circuit
the relay is attached to or the relays
purpose
Up to 16 characters
DAD-N-101
1.2 CT/VT Config Menu
Description Range
Default
Setting
CT Input
Selects whether 1 or 5 Amp terminals
are being used
1,5 A
1 A
CT Ratio
CT ratio to scale primary current
instruments
5:0.2…5000:7 2000:1
1.3 Differential Menu
Description Range
Default
Setting
87/50-1 Element
Disabled, Enabled
Disabled
Содержание 7SG12 DAD-N